H3Y-4-B DC100-110 60S | Omron DC100-110 Sixty-Second Timer https://www.googletagmanager.com/gtag/js?id=AW-11114891143
+91 79955 44066 sales@indmall.in

H3Y-4-B DC100-110 60S: Omron DC100-110 Sixty-Second Timer

Technical Specifications of Omron DC100-110 Sixty-Second Timer H3Y-4-B DC100-110 60S:

SpecValue
Rated power supply voltage100 to 110 VDC If power supply incorporates a single-phase full-wave rectifier.
Allowable voltage variable range85 to 110% of the power supply voltage
Power consumptionApprox. 1.3 W (at 110 VDC)
Reset voltage10% min, of rated supply voltage

Omron DC100-110 Sixty-Second Timer H3Y-4-B DC100-110 60S Technical Specifications:

SpecificationValue
Rated power supply voltage100 to 110 VDC If power supply incorporates a single-phase full-wave rectifier.
Allowable voltage variable range85 to 110% of the power supply voltage
Power consumptionApprox. 1.3 W (at 110 VDC)
Reset voltage10% min, of rated supply voltage
Number of time ranges1
Operation modePower ON-delay
Control output (Type)Time-limit: 4PDT
Control output (Contact output)Resistive load: 3 A at 250 VAC (cosφ=1) Minimum applicable load: 1 mA at 1 VDC (failure level: P)
Operating resettingTime-limit operation/Self-reset
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Ambient humidity rangeOperating: 35 to 85%
Accuracy of operating time±1% FS max.
Setting error±10% FS ±50 ms max.
Reset time0.1 s max. (including halfway reset)
Influence of voltage±2% FS ±10 ms max.
Influence of temperature±2% FS ±10 ms max.
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying terminals and exposed non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min (Terminal screw sections are not excluded) Between operating power circuit and control output: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 1,500 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 3 kV Between current carrying terminals and exposed non-current carrying metal parts: 4.5 kV
Noise immunity±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunityMulfunction: 4 kV, Destruction: 8 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 1 hour Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions
Life expectancy (relay output)Electrical: 200,000 operations min. (3 A at 250 VAC, resistive load at 1800 operations/h, Room temperature) Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Degree of protectionIP40
Connecting method14-pin round socket (Push-In Plus Terminal Block)
Case colorBlack
WeightApprox. 50 g
Send Your Inquiry for Omron DC100-110 Sixty-Second Timer, H3Y-4-B DC100-110 60S with cost-effective solutions. Essential Technical Specs of H3Y-4-B DC100-110 60S cover Operating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing), Resistive load: 3 A at 250 VAC (cosφ=1) Minimum applicable load: 1 mA at 1 VDC (failure level: P), Time-limit: 4PDT, Power ON-delay. It also delivers Approx. 50 g, 85 to 110% of the power supply voltage, 100 to 110 VDC If power supply incorporates a single-phase full-wave rectifier.. Capture the Best Deal with a Quote for your requirement of Omron DC100-110 Sixty-Second Timer. Our pricing and support are designed to exceed the standards of other Traders & Suppliers.