H3Y-2-B AC200-230 10M: Omron High-Volt Medium Timer
Technical Specifications of Omron High-Volt Medium Timer H3Y-2-B AC200-230 10M:
Spec | Value |
---|---|
Rated power supply voltage | 200 to 230 VAC 50/60 Hz |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power consumption | Approx. 1.8 VA (at 230 VAC) |
Reset voltage | 10% min, of rated supply voltage |
Omron High-Volt Medium Timer H3Y-2-B AC200-230 10M Technical Specifications:
Specification | Value |
---|---|
Rated power supply voltage | 200 to 230 VAC 50/60 Hz |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power consumption | Approx. 1.8 VA (at 230 VAC) |
Reset voltage | 10% min, of rated supply voltage |
Number of time ranges | 1 |
Operation mode | Power ON-delay |
Control output (Type) | Time-limit: DPDT |
Control output (Contact output) | Resistive load: 250 VAC 5 A (cosφ=1) Minimum applicable load: 1 mA at 5 VDC (failure level: P) |
Operating resetting | Time-limit operation/Self-reset |
Ambient temperature range | Operating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing) |
Ambient humidity range | Operating: 35 to 85% |
Accuracy of operating time | ±1% FS max. |
Setting error | ±10% FS ±50 ms max. |
Reset time | 0.1 s max. (including halfway reset) |
Influence of voltage | ±2% FS ±10 ms max. |
Influence of temperature | ±2% FS ±10 ms max. |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | Between current carrying terminals and exposed non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min (Terminal screw sections are not excluded) Between operating power circuit and control output: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
Send Your Inquiry for Omron High-Volt Medium Timer, H3Y-2-B AC200-230 10M with cost-effective solutions. Essential Technical Specs of H3Y-2-B AC200-230 10M cover Operating: -10 to 55 ℃ (with no icing)
Storage: -25 to 65 ℃ (with no icing), Resistive load: 250 VAC 5 A (cosφ=1)
Minimum applicable load: 1 mA at 5 VDC (failure level: P), Time-limit: DPDT, Power ON-delay. It also delivers Approx. 50 g, 85 to 110% of the power supply voltage, 200 to 230 VAC 50/60 Hz. Capture the Best Deal with a Quote for your requirement of Omron High-Volt Medium Timer. Our pricing and support are designed to exceed the standards of other Traders & Suppliers.