Procurement teams shortlist MY2N-AC24 with Omron SMPS 24V 10A, My2N Gs Dc24 and Phoenix Slim Relay, aligning budget approvals, warranty terms, and multisite availability for smoother rollout across plants.
Omron MY2N AC24 Relay
The Omron MY2N AC24 Relay delivers reliable switching performance with a Closed type (cover) protective housing, Plug-in terminal structure compatible with a Socket for secure mounting. It provides a DPDT contact form with a Single contact method. Supporting a max contact current of AC: 5 A DC: 5 A loads. Built with a 180 Ξ© coil resistance, it ensures dependable response with an 80% max. operate voltage and 30 % min. release voltage. Supporting 250 VAC 125 VDC maximum contact voltage. Manufactured by Omron, listed under Omron Relay solutions, this model belongs to theMY Series.

| Brand | Omron |
| Product Type | Relay |
| Model Number | MY2N AC24 |
Omron MY2N AC24 Relay - Technical Specifications
| Specification | Value |
|---|---|
| Terminal structure | Plug-in terminal |
| Degree of protection | Closed type (cover) |
| Coil resistance | 180 Ξ© |
| Operate voltage (Set voltage) | 80% max. |
| Release voltage (Reset voltage) | 30 % min. |
| Power consumption Operate / Release | Approx. 0.9 to 1.3 VA 60 Hz |
| Contact rated load | 220 VAC 5 A (Resistive load) 220 VAC 2 A (Inductive load (cosΟ = 0.4)) 24 VDC 5 A (Resistive load) 24 VDC 2 A (Inductive load (L/R = 7 ms)) |
| Max. contact voltage | 250 VAC 125 VDC |
| Max. Contact Current | AC: 5 A DC: 5 A |
| Maximum switching power | 1100 VA (Resistive load) 440 VA (Inductive load (cosΟ = 0.4)) 120 W (Resistive load) 48 W (Inductive load (L/R = 7 ms)) |
| Contact method | Single |
| Contact form | DPDT |
| Contact resistance | 50 mΞ© max. (Voltage drop method with 5 VDC 1 A) |
| Operating time | 20 ms max. (With rated operating power applied, not including contact bounce) |
| Reset time | 20 ms max. (With rated operating power applied, not including contact bounce) |
| Maximum operating frequency | Mechanical: 18000 time/hour Rated load: 1800 time/hour |
| Ambient temperature (Operating) | -55 to 60 β (with no freezing or condensation) |
| Ambient humidity (Operating) | 5 to 85% |
| Mounting method | Socket |
| Operating indicator | LED |
| Coil ratings | 24 VAC 50 Hz 53.8 mA 24 VAC 60 Hz 46 mA |