Delta DRP-24V240W1CAN 10A 24V DIN Rail Power Supply
The Delta DRP-24V240W1CAN is a reliable 10A 24V DIN Rail Power Supply ideal for industrial automation, control panels, and machinery that require stable DC power. It delivers 10A output current at 24V with 240W power, supporting a wide input voltage range of 88–264Vac and frequency compatibility of 47–63Hz. Manufactured by Delta industrial automation products, this model is part of the Delta power supply solutions and belongs to the DIN Rail CliQ III series, offering compact, efficient, and dependable DC power for automation systems.

| Brand | Delta |
| Product Type | SMPS |
| Product | DRP-24V240W1CAN |
Delta 3.8A 91W DIN Rail Power Supply DRP-24V100W1NN Technical Specifications:
| Specification | Value |
|---|---|
| Output Current | 10A |
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 24-28Vdc |
| Output Power | 240W |
| Line Regulation | 0.5% (@ 88-264Vac input, 100% load) |
| Load Regulation | 1% (@ 88-264Vac input, 0-100% load) |
| PARD | 100mVpp Max. |
| Start-up Time | 1,000ms Max. @ 24V, 10A |
| Hold-up Time | 24ms Typ. @ 24V, 10A 20ms min. @ 24V, 10A |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 0-100% load Slew rate 0.1A/µs (@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle) |
| Start-up with Capacitive Loads | 10,000µF |
| Rise Time | 60ms Max. @ 24V, 10A |
| Power Boost Duration | 5 seconds Min. |
| Power Boost Recovery Time | 18 seconds Typ. |
| Nominal Input Voltage | 100-240Vac |
| Input Voltage Range | 88-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 100-375Vdc (Continuously operating, with safety approval according to IEC/EN/UL 60950-1) 88-100Vdc (With power de-rating) |
| Input Current | 2.27A Typ. @ 115 Vac, 1.19A Typ. @ 230Vac |
| Efficiency at 100% load | 92.70% Typ. @ 115Vac, 94.48% Typ. @ 230Vac |
| Inrush Current | (Cold Start) 11.0A Typ. @ 115Vac, 24.4A Typ. @ 230Vac, 33A Max. @ 115Vac, 65A Max. @ 230Vac |
| Power Factor at 100% load | 0.99 Typ. @ 115Vac, 0.93 Typ. @ 230Vac, 0.99 Min. @ 115Vac, 0.93 Min. @ 230Vac |
| Leakage Current | (Enclosure to Neutral) < 0.25mA / 0.80mA: 110Vac, 50Hz, TN/TT system / IT system < 0.38mA / 1.00mA: 132Vac, 50Hz, TN/TT system / IT system < 0.74mA / 2.00mA: 264Vac, 50Hz, TN/TT system / IT system |
| Power Dissipation | At 24V, 0A: 3.54W Typ. @ 115Vac, 2.90W Typ. @ 230Vac, 6.0W Max. @ 115Vac, 6.0W Max. @ 230Vac At 24V, 10A: 18.97W Typ. @ 115Vac, 14.05W Typ. @ 230Vac, 21.0W Max. @ 115Vac, 16.0W Max. @ 230Vac |
| Case Chassis / Cover | Aluminium |
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Input Terminal | 3 Pins (Rated 600V/35A) |
| Output Terminal | 4 Pins (Rated 300V/28A) |
| Signal Terminal | 2 Pins (Rated 300V/28A) |
| Noise Sound Pressure Level (SPL) | < 25dBA |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Wire | Input: AWG 18-8 Output: AWG 16-12 Signal: AWG 16-12 |
| Unit Weight | 0.84 kg (1.85 lb) |
| Operating Temperature | -25°C to +70°C (Cold start -40°C) |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | Vertical Mounting: > 60°C de-rate power by 2.5% / °C Horizontal Mounting: > 40°C de-rate power by 2.5% / °C Input Voltage: AC input < 100Vac de-rate power by 0.83% / V DC input < 100Vdc de-rate power by 1.67% / V |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Pollution Degree | 2 |
| Bump Test (Operating) | IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total |
| Over Voltage Category | III (operating altitude 2,500 Meters) II (operating altitude 5,000 Meters) According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
The Delta DRP-24V240W1CAN 10A 24V DIN Rail Power Supply is designed for integration into industrial control panels, factory automation systems, and machinery where reliable DC power distribution is crucial. Its DIN rail mounting ensures organized installation in tight panel spaces, while robust input and output terminals guarantee secure and stable electrical connections. This makes the unit ideal for continuous operation in industrial environments requiring high uptime.
Built for harsh conditions, the DRP-24V240W1CAN operates within -25°C to +70°C, with cold-start capability down to -40°C and storage temperature support up to +85°C. The green LED (DC OK) indicator allows quick verification of power status and operational health. Rated terminals (600V/35A for input and 300V/28A for output) ensure safe and dependable performance under varying loads.
For engineers and automation specialists, the Delta DRP-24V240W1CAN provides consistent 10A output at 24V with 240W power, enabling seamless integration into industrial systems. Its compact, efficient design ensures reliable operation, while the unit’s durability supports long-term industrial usage. Request a quote today to secure competitive pricing and dedicated support for this premium 10A 24V DIN Rail Power Supply, ensuring uninterrupted performance for your automation applications.