LC1K12105B7: Schneider TeSys K Contactor 12A 24VAC Coil
Technical Specifications of Schneider TeSys K Contactor 12A 24VAC Coil LC1K12105B7:

| Power pole contact composition | 3 NO |
| Control Circuit Type | AC 50/60 Hz |
| Inrush power in W | - |
| Connection Terminals | solder pins 0.001 in (0.035 mm)) |
Schneider TeSys K Contactor 12A 24VAC Coil LC1K12105B7 Technical Specifications:
| Specification | Value |
|---|---|
| Range | TeSys |
| Product or Component Type | Contactor |
| Device short name | LC1K |
| Contactor application | Resistive loadMotor control |
| Utilisation category | AC-3AC-3eAC-1AC-4 |
| Poles description | 3P |
| Power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz |
| [Ie] rated operational current | 12 A (at <140 ยฐF (60 ยฐC)) at <= 440 V AC AC-3 for power circuit12 A (at <140 ยฐF (60 ยฐC)) at <= 440 V AC AC-3e for power circuit20 A (at <140 ยฐF (60 ยฐC)) at <= 690 V AC AC-1 for power circuit |
| Control circuit type [Uc] | AC 50/60 Hz |
| Control circuit voltage | 24 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 140 ยฐF (60 ยฐC)) for power circuit10 A (at 122 ยฐF (50 ยฐC)) for signalling circuit |
| Irms rated making capacity | 144 A AC for power circuit conforming to IEC 60947110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 115 A 122 ยฐF (50 ยฐC) - 1 s for power circuit105 A 122 ยฐF (50 ยฐC) - 5 s for power circuit100 A 122 ยฐF (50 ยฐC) - 10 s for power circuit75 A 122 ยฐF (50 ยฐC) - 30 s for power circuit55 A 122 ยฐF (50 ยฐC) - 1 min for power circuit50 A 122 ยฐF (50 ยฐC) - 3 min for power circuit25 A 122 ยฐF (50 ยฐC) - >= 15 min for power circuit80 A - 1 s for signalling circuit90 A - 500 ms for signalling circuit110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at <= 440 V for power circuit25 A aM for power circuit10 A gG for signalling circuit conforming to IEC 6094710 A gG for signalling circuit conforming to VDE 0660 |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-5-1Signalling circuit 600 V UL 508Power circuit 600 V CSA C22.2 No 14Signalling circuit 600 V CSA C22.2 No 14 |
| Inrush power in W | - |
| Hold-in power consumption in W | - |
| Heat dissipation | 1.3 W |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at <122 ยฐF (50 ยฐC))Drop-out: >= 0.20 Uc (at <122 ยฐF (50 ยฐC)) |
| Connections - terminals | solder pins 0.001 in (0.035 mm)) |
| Maximum operating rate | 3600 cyc/h |
| Mounting Support | Printed circuit boards |
| Operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing |
| Height | 2.3 in (58 mm) |
| Width | 1.8 in (45 mm) |
| Depth | 2.2 in (57 mm) |
| Net Weight | 0.40 lb(US) (0.18 kg) |
| IP degree of protection | IP2X VDE 0106 |
| Ambient air temperature for operation | - |
| Ambient Air Temperature for Storage | -58โฆ176 ยฐF (-50โฆ80 ยฐC) |
| Operating altitude | 6561.68 ft (2000 m) without derating |
Please speak to our Technical Engineer for Schneider TeSys K Contactor 12A 24VAC Coil LC1K12105B7 at attractive prices. Technical Specs Summary of LC1K12105B7 includes Contactor Product or Component Type 3 NO power pole contact composition. This contactor operates with a rated operational voltage of up to Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz, ensuring flexibility in various industrial applications. The control circuit operates on a AC 50/60 Hz with a control voltage of 24 V AC 50/60 Hz, providing reliable control functionality. It has a rated impulse withstand voltage of 8 kV, conforming to industry standards for electrical safety. The compact design includes a height of 2.3 in (58 mm), a width of 1.8 in (45 mm), and a depth of 2.2 in (57 mm). Match Your Needs with a Quote for your requirement of Schneider TeSys K Contactor 12A 24VAC Coil. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.