Technical Specifications of Schneider 2 HP 3 Phase VFD ATV212HU15N4:

SpecValue
Connector Type1 open style1 RJ45
Motor power range AC-31.1…2 kW at 380…440 V 3 phases1.1…2 kW at 480…500 V 3 phases
Switching Frequency6...16 kHz adjustable12...16 kHz with derating factor
Power Consumption in W78 W

Schneider 2 HP 3 Phase VFD ATV212HU15N4 Technical Specifications:

SpecificationValue
Connector Type1 open style1 RJ45
Minimum switching current3 mA at 24 V DC for configurable relay logic
Motor power range AC-31.1…2 kW at 380…440 V 3 phases1.1…2 kW at 480…500 V 3 phases
Net weight2 kg
Switching frequency6...16 kHz adjustable12...16 kHz with derating factor
Output voltage<= power supply voltage
Supply voltage limits323…528 V
Operating positionVertical +/- 10 degree
Discrete input typeF programmable 24 V DC, with level 1 PLC, impedance: 4700 OhmR programmable 24 V DC, with level 1 PLC, impedance: 4700 OhmRES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Speed range1…10
[Us] rated supply voltage380...480 V - 15...10 %
Supply frequency50...60 Hz - 5...5 %
IP degree of protectionIP20 on upper part without blanking plate on cover conforming to IEC 61800-5-1IP20 on upper part without blanking plate on cover conforming to IEC 60529IP21 conforming to IEC 61800-5-1IP21 conforming to IEC 60529IP41 on upper part conforming to IEC 61800-5-1IP41 on upper part conforming to IEC 60529
Power dissipation in W78 W
Network frequency47.5...63 Hz
Electrical connectionVIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10
EMC filterClass C2 EMC filter integrated
Motor starter typeVariable speed drive
Depth150 mm
Range of productAltivar 212
Nominal switching frequency12 kHz
Discrete output typeConfigurable relay logic: (FLA, FLC) NO - 100000 cyclesConfigurable relay logic: (FLB, FLC) NC - 100000 cyclesConfigurable relay logic: (RY, RC) NO - 100000 cycles
Acceleration and deceleration rampsLinear adjustable separately from 0.01 to 3200 sAutomatic based on the load
Warranty18 months
Insulation resistance>= 1 mOhm 500 V DC for 1 minute
Frequency resolutionDisplay unit: 0.1 HzAnalog input: 0.024/50 Hz
Tightening torque1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Transmission rate9600 bps or 19200 bps
Assembly styleWith heat sink
Motor power hp2 hp
Dielectric strength3535 V DC between earth and power terminals5092 V DC between control and power terminals
Regulation loopAdjustable PI regulator
Speed drive output frequency0.5…200 Hz
Analogue output typeFM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bitsFM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
Analogue input typeVIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bitsVIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bitsVIB configurable PTC probe: 0...6 probes, impedance: 1500 OhmVIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
Ambient air temperature for storage-25…70 °C
Type of cableWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPRWithout mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVCWith UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Type of polarizationNo impedance
Motor power kW1.5 kW
Variable speed drive application selectionBuilding - HVAC compressor for scrollBuilding - HVAC fanBuilding - HVAC pump
Email us for your Schneider 2 HP 3 Phase VFD ATV212HU15N4 needs at budget-friendly prices. Key technical specifications of the ATV212HU15N4 include a minimum switching current of 3 mA at 24 V DC with configurable relay logic. The switching frequency can be adjusted between 6...16 kHz, or 12...16 kHz with a derating factor. Operating within a supply voltage range of 323…528 V, it maintains a vertical position within +/- 10 degrees. Supporting a speed range of 1…10, the VFD operates on a rated supply voltage [Us] of 380...480 V, with a tolerance of -15...+10 %, and a supply frequency of 50...60 Hz within -5...+5 % tolerance. Designed to integrate seamlessly with variable speed drives, it delivers optimal performance at 12 kHz. Get a tailored quote for your Schneider 2 HP 3 Phase VFD and enjoy our competitive pricing and superior support that set us apart from other suppliers.