Technical Specifications of Disconnect terminal block PTVC 2,5-MT BU 1079060

BrandPhoenix Contact
Product TypeTerminal Block
ProductPTVC 2,5-MT BU

Phoenix Contact Disconnect terminal block PTVC 2,5-MT BU, 1079060 Technical Specifications

SpecificationValue
Product typeDisconnect terminal block
DIN rail/fixing supportNS 35/15
Number of connections2
Number of rows1
Potentials1
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Maximum power dissipation for nominal condition0.77 W
Number of connections per level2
Nominal cross section2.5 mm²
Stripping length8 mm ... 10 mm
Internal cylindrical gageA3
Connection in acc. with standardIEC 6094771
Conductor cross section rigid1 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]26 ... 14 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)2.5 mm² ...
Flexible conductor cross section (ferrule with plastic sleeve)2.5 mm² ...
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve1 mm²
Nominal current20 A (at 2.5 mm²)
Maximum load current20 A (with 4 mm² conductor cross section, rigid)
Nominal voltage400 V
Width5.2 mm
End cover width2.2 mm
Height50.8 mm
Depth on NS 35/7,536.8 mm
Depth on NS 35/1544.3 mm
Colorblue (RAL 5015)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Test voltage setpoint1.89 kV
ResultTest passed
Requirement temperature-rise testIncrease in temperature ≤ 45 K
Short-time withstand current 2.5 mm²0.3 kA
Open side panelYes
DIN rail/fixing supportNS 35
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
Temperature cycles192
Time of exposure30 s
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
SpecificationDIN EN 50155 (VDE 0115200):201805
SpectrumLong life test category 2, bogiemounted
Frequencyf1 = 5 Hz to f2 = 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration30g
Test duration per axis5 h
Test directionsX, Y and Zaxis (pos. and neg.)
Pulse shapeHalfsine
Shock duration18 ms
Number of shocks per direction3
NoteThe maximum load current of a single clamping unit must not be exceeded.
Depth35.3 mm
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve)0.5 mm² ... 1 mm²