+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact PT 4-PE/L/MT - 3002617 - Ground terminal block

Technical Specifications of Ground terminal block PT 4-PE/L/MT 3002617

BrandPhoenix Contact
Product TypeTerminal Block
ProductPT 4-PE/L/MT

Phoenix Contact Ground terminal block PT 4-PE/L/MT, 3002617 Technical Specifications

SpecificationValue
Product typeGround terminal block
DIN rail/fixing supportNS 35/15
Number of connections5
Number of rows3
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Maximum power dissipation for nominal condition1.02 W
Number of connections per level2
Nominal cross section4 mm²
Stripping length10 mm ... 12 mm
Internal cylindrical gageA4
Connection in acc. with standardIEC 6094773
Conductor cross section rigid0.5 mm² ... 6 mm²
Cross section AWG24 ... 10 (converted acc. to IEC)
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section, flexible [AWG]24 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.5 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1 mm²
Nominal current20 A
Maximum load current20 A (6 mm²)
Nominal voltage500 V
Width6.2 mm
Height119.5 mm
Depth on NS 35/7,557.6 mm
Depth on NS 35/1565.1 mm
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 HL 3
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Test voltage setpoint1.89 kV
ResultTest passed
Requirement temperature-rise testIncrease in temperature ≤ 45 K
Short-time withstand current 2.5 mm²0.3 kA
Short-time withstand current 4 mm²0.48 kA
Open side panelYes
DIN rail/fixing supportNS 35
Test force setpoint1 N
Rotation speed10 rpm
Revolutions135
Conductor cross section/weight0.2 mm² / 0.2 kg
Temperature cycles192
Time of exposure30 s
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
SpecificationDIN EN 50155 (VDE 0115200):200803
SpectrumLong life test category 1, class B, body mounted
Frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level0.964 (m/s²)²/Hz
Acceleration5g
Test duration per axis5 h
Test directionsX, Y and Zaxis (pos. and neg.)
Pulse shapeHalfsine
Shock duration30 ms
Number of shocks per direction3
Rated cross section AWG12
Depth54.5 mm
Product familyPT
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve)0.5 mm² ... 1 mm²
Short-time withstand current 6 mm²0.72 kA
output(Permanent)
IdentificationX II 3 G Ex ec llC Gc
Operating temperature range60 °C ... 125 °C
Operating cycles of the disconnect knife100
Ex-certified accessories3002619 DPT 4PE/L/HESI
List of bridgesPlugin bridge / FBS 26 / 3030336
Bridge data19 A / 4 mm²
Rated voltage275 V
Rated current20 A (4 mm²)
Contact resistance1.7 mΩ
Connection capacity rigid0.2 mm² ... 6 mm²
Connection capacity AWG24 ... 12
Connection capacity flexible0.2 mm² ... 4 mm²
Conductor cross section, rigid [AWG]20 ... 10 (converted acc. to IEC)
Rated insulation voltage250 V
Temperature increase35 K (20 A/4 mm²)
- At bridging between non-adjacent terminal blocks275 V
- At cut-to-length bridging with cover275 V

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.