+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact PT 4-PE/L/HEDI - 3002606 - Ground terminal block

Technical Specifications of Ground terminal block PT 4-PE/L/HEDI 3002606

BrandPhoenix Contact
Product TypeTerminal Block
ProductPT 4-PE/L/HEDI

Phoenix Contact Ground terminal block PT 4-PE/L/HEDI, 3002606 Technical Specifications

SpecificationValue
Product typeGround terminal block
DIN rail/fixing supportNS 35/15
Number of connections5
Number of rows3
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Maximum power dissipation for nominal condition1.02 W
Number of connections per level2
Nominal cross section4 mm²
Stripping length10 mm ... 12 mm
Internal cylindrical gageA4
Connection in acc. with standardIEC 6094771
Conductor cross section rigid0.5 mm² ... 6 mm²
Cross section AWG24 ... 10 (converted acc. to IEC)
Conductor cross section flexible0.2 mm² ... 6 mm²
Conductor cross section, flexible [AWG]24 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.5 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 4 mm²
Nominal current20 A
Maximum load current18 A (6 mm²)
Nominal voltage500 V
Width6.2 mm
Height82.6 mm
Colorblack (RAL 9005)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 HL 3
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
ResultTest passed
Open side panelYes
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
SpecificationDIN EN 50155 (VDE 0115200):200803
SpectrumLong life test category 1, class B, body mounted
Frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level0.964 (m/s²)²/Hz
Acceleration5g
Test duration per axis5 h
Test directionsX, Y and Zaxis (pos. and neg.)
Pulse shapeHalfsine
Shock duration30 ms
Number of shocks per direction3
Rated cross section AWG12
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve)0.5 mm² ... 1 mm²
output(Permanent)
IdentificationX II 3 G Ex ec llC Gc
Operating temperature range60 °C ... 130 °C
Ex-certified accessories3002619 DPT 4PE/L/HESI
List of bridgesPlugin bridge / FBS 26 / 3030336
Bridge data18 A / 4 mm²
Rated voltage275 V
Rated current18 A (4 mm²)
Contact resistance2 mΩ
Connection capacity rigid0.2 mm² ... 6 mm²
Connection capacity AWG24 ... 12
Connection capacity flexible0.2 mm² ... 4 mm²
Conductor cross section, rigid [AWG]20 ... 10 (converted acc. to IEC)
Conductor cross section flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1 mm²
Rated insulation voltage250 V
Temperature increase35.5 K (18 A / 4 mm²)
- At bridging between non-adjacent terminal blocks275 V
- At cut-to-length bridging with cover275 V