Technical Specifications of Ground terminal block PT 2,5-PE/L/N/MT 1336376

BrandPhoenix Contact
Product TypeTerminal Block
ProductPT 2,5-PE/L/N/MT

Phoenix Contact Ground terminal block PT 2,5-PE/L/N/MT, 1336376 Technical Specifications

SpecificationValue
Product typeGround terminal block
DIN rail/fixing supportNS 35/15
Number of connections8
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Number of connections per level2
Nominal cross section2.5 mm²
Stripping length8 mm ... 10 mm
Internal cylindrical gageA3
Connection in acc. with standardIEC 6094772
Conductor cross section rigid0.34 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.5 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]26 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.5 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 2.5 mm²
Nominal current18 A
Maximum load current20 A (with 4 mm² conductor crosssection)
Nominal voltage500 V
Width5.2 mm
End cover width2.2 mm
Height142.4 mm
Depth on NS 35/7,570.2 mm
Depth on NS 35/1577.7 mm
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Test voltage setpoint1.89 kV
ResultTest passed
Requirement temperature-rise testIncrease in temperature ≤ 45 K
Short-time withstand current 2.5 mm²0.3 kA
Open side panelYes
DIN rail/fixing supportNS 35
Rotation speed10 (+/ 2) rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
Temperature cycles192
Time of exposure30 s
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
SpecificationDIN EN 50155 (VDE 0115200):202206
SpectrumService life test category 1, class B, body mounted
Frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level0.964 (m/s²)²/Hz
Acceleration5g
Test duration per axis5 h
Test directionsX, Y and Zaxis (pos. and neg.)
Pulse shapeHalfsine
Shock duration30 ms
Number of shocks per direction3
Number of positions4
Conductor cross section, rigid [AWG]20 ... 12 (converted acc. to IEC)