+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact PSR-UNI-L-2X2NO-2DO-24DC-PI - 1487644 - Safety relays

Technical Specifications of Safety relays PSR-UNI-L-2X2NO-2DO-24DC-PI 1487644

BrandPhoenix Contact
Product TypeSafety Relays
ProductPSR-UNI-L-2X2NO-2DO-24DC-PI

Phoenix Contact Safety relays PSR-UNI-L-2X2NO-2DO-24DC-PI, 1487644 Technical Specifications

SpecificationValue
Product typeSafety relays
Product familyPSRuni
ApplicationEmergency stop
Control1 and 2 channel
Mechanical service life10x 106 cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Overvoltage categoryIII (Between logic and enabling current paths)
Degree of pollution2
Typical response time< 100 ms (Automatic/manual start)
Typ. starting time with Us1 s (when controlled via A1; applicative control via A1/A2 is not permitted)
Typical release time< 25 ms (on demand via the sensor circuit)
Restart time< 1 s (Boot time)
Recovery time500 ms (following demand of the safety function)
Start pulse lengthmin. 500 ms (manual start)
Maximum power dissipation for nominal condition9.15 W (At US = 30 V, ILΒ² = 144 AΒ², configured functions: mode 1 = 2, mode 2 = 2)
Nominal operating mode100% operating factor
Rated insulation voltage250 V
Rated surge voltage/insulationSee section β€œInsulation coordination”
Description of the inputnon-safety-related
Number of inputs2
Input voltage range "1" signal11 V DC ... 30 V DC
Inrush currentmin. 3 mA
Filter timemax. 3 ms (Test pulse width of low test pulses)
Max. permissible overall conductor resistance150 Ξ©
Protective circuitReverse polarity protection Suppressor diode
Current consumption< 3.5 mA (typ. with US)
Output descriptionnon-safety-related
Number of outputs2
Contact switching type4 enabling current paths
Contact materialAgCuNi +0.2 Β΅m ... 0.4 Β΅m Au / AgSnO2 +0.2 Β΅m Au
Switching voltagemin. 10 V AC/DC
Switching capacitymin. 60 mW
Limiting continuous current6 A
Sq. Total current144 A2 (K1 = 72 AΒ², K2 = 72 AΒ², observe derating)
Switching frequencymax. 0.1 Hz
Output fuse6 A gL/gG
pluggableyes
Connection methodPush-in connection
Conductor cross section rigid0.2 mmΒ² ... 2.5 mmΒ²
Conductor cross section flexible0.2 mmΒ² ... 2.5 mmΒ²
Conductor cross-section AWG24 ... 14
Stripping length10 mm
Status display4 x LED (green, yellow, red)
Operating voltage display1 x LED (green, yellow, red)
Width22.5 mm
Height117.5 mm
Depth114.5 mm
Housing materialFrianyl B63 V0 GV30
Category4 (5 A DC13; 3 A AC15; 8760 cycles/year)
Performance level (PL)e
Safety Integrity Level (SIL)3
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Ambient temperature (operation)-25 Β°C ... 60 Β°C (observe derating)
Ambient temperature (storage/transport)-40 Β°C ... 85 Β°C
Maximum altitude≀ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
Mounting typeDIN rail mounting
Mounting positionvertical or horizontal
Rated control circuit supply voltage US24 V DC -20 % / +25 %
Rated control supply current IStyp. 65 mA (When sensor circuit and start circuit are controlled internally)
Power consumption at UStyp. 1.32 W
Input voltage range "0" signal0 V DC ... 5 V DC
Input current range "0" signal0 mA ... 1.5 mA
Concurrence∞ (2-channel wiring), 5 s (non-equivalent wiring), 0.5 s (two-hand control)
Assembly noteSee derating curve
Maximum inrush current500 mA (Ξ”t = 10 ms at Us)
DesignationA1/A2
Voltagetyp. (US - 2,5 V)
Currentmax. 100 mA
Limit frequencymin. 0 Hz
Ohmic loadmin. 192 Ξ© (max.100 mA)
Short-circuit protectionYes
Discharging circuitno
Cable lengthSee inputs
Error indication1 x LED (red)
Coloryellow (RAL 1018)

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.