| Note on application | Only for industrial use |
| Product type | Safety relays |
| Product family | PSRclassic |
| Application | Extension module |
| Output fuse | max. 6 A |
| Control | 1-channel |
| Mechanical service life | 10x 106 cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Maximum power dissipation for nominal condition | 16.14 W (UN = 26.4 V, IL² = 72 A², PTotal max = 1.74 W + 14.4 W) |
| Nominal operating mode | 100% operating factor |
| Rated insulation voltage | 250 V |
| Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit/N/C contacts and enabling current paths). |
| Typ. starting time with Us | 10 ms (when controlled via K1/K2) |
| Typical release time | 10 ms (when requested via K1/K2) |
| Operating voltage display | 1 x LED (green) |
| Contact switching type | 2 N/C contacts in series, floating |
| Contact material | AgSnO2 |
| Limiting continuous current | 1 A |
| Sq. Total current | 1 A2 |
| Switching capacity | min. 50 mW |
| Output fuse | 1 A (gL/gG) |
| pluggable | yes |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Width | 22.5 mm |
| Height | 112 mm |
| Depth | 114.5 mm |
| Color (Housing) | yellow (RAL 1018) |
| Housing material | PA |
| Category | 4 (In conjunction with suitable evaluating device) |
| Performance level (PL) | e (5 A DC13; 5 A AC15; 8760 switching cycles/year) |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Mounting type | DIN rail mounting |
| Mounting position | any |
| Inrush current | min. 10 mA |
| Protective circuit | Suppressor diode |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Output description | 2 N/C contacts in parallel, floating |
| Number of outputs | 1 |
| Switching frequency | max. 0.5 Hz |
| Identification | CE-compliant |
| Switching voltage | min. 5 V AC/DC |
| Number of inputs | 1 |
| Current consumption | typ. 60 mA |
| Description of the input | safety-related |