+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact PSR-MC40-3NO-1DO-24DC-SC - 2700569 - Safety relays

Technical Specifications of Safety relays PSR-MC40-3NO-1DO-24DC-SC 2700569

BrandPhoenix Contact
Product TypeSafety Relays
ProductPSR-MC40-3NO-1DO-24DC-SC

Phoenix Contact Safety relays PSR-MC40-3NO-1DO-24DC-SC, 2700569 Technical Specifications

SpecificationValue
Note on applicationOnly for industrial use
Product typeSafety relays
Product familyPSRmini
ApplicationEmergency stop
Control2-channel
Mechanical service life10x 106 cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Overvoltage categoryIII
Degree of pollution2
Typical response time< 175 ms (automatic start)
Typ. starting time with Us< 250 ms (when controlled via A1)
Typical release time< 20 ms (on demand via the sensor circuit)
Restart time< 1 s (Boot time)
Recovery time< 500 ms
Start pulse length≥ 500 ms (manual start)
Maximum power dissipation for nominal condition4.8 W (US = 26.4 V, IL² = 48 A², PTotal max = 2.4 W + 2.4 W)
Nominal operating mode100% operating factor
Rated insulation voltage250 V AC
Rated surge voltage/insulationSee section “Insulation coordination”
Description of the inputnon-safety-related
Number of inputs1
Input voltage range "1" signal20.4 V DC ... 26.4 V DC
Inrush currentmin. 3 mA
Filter timemax. 1.5 ms (Test pulse width of low test pulses)
Max. permissible overall conductor resistance150 Ω
Protective circuitSuppressor diode
Current consumption< 10 mA (typ. with US at S34/24 V)
Output descriptionnon-safety-related
Number of outputs1 (digital, PNP)
Contact switching type3 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 12 V AC/DC
Switching capacitymin. 60 mW
Limiting continuous current6 A
Sq. Total current48 A2 (observe derating)
Switching frequency0.1 Hz
Output fuse6 A gL/gG
pluggableyes
Connection methodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3
Status display3 x LED (green)
Operating voltage display1 x LED (green)
Width12.5 mm
Height112.2 mm
Depth114.5 mm
Color (Housing)yellow (RAL 1018)
Housing materialPA
Category4
Performance level (PL)e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Safety Integrity Level (SIL)3
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Ambient temperature (operation)-40 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (operation)10 Hz ... 150 Hz, amplitude 0.15 mm, 2g
IdentificationCE-compliant
Mounting typeDIN rail mounting
Mounting positionvertical or horizontal
Rated control circuit supply voltage US24 V DC -15 % / +10 %
Rated control supply current IStyp. 80 mA
Power consumption at UStyp. 1.92 W
Input voltage range "0" signal0 V DC ... 5 V DC (for safe Off; at S12 and S22)
Input current range "0" signal0 mA ... 2 mA (for safe Off; at S12 and S22)
Concurrence
Tightening torque0.5 Nm ... 0.6 Nm
Assembly noteSee derating curve
Maximum inrush current500 mA (Δt = 1 ms at Us)
DesignationA1/A2
Voltage22 V DC (Us - 2 V)
Currentmax. 100 mA