+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Omron H3CR-FN AC100-240/DC100-125 Timer

The Omron H3CR-FN AC100-240/DC100-125 Timer is built for dependable timing control with an allowable voltage variable range of 85 to 110% of the power supply voltage and an operation start voltage of 10% max. of rated supply voltage. It supporting 18 time ranges for dependable performance. Designed for Flicker OFF start operation, it provides a reliable DPDT time-limit control output through an 11-pin round socket connection. Manufactured by Omron, listed under Omron Timers, and part of the H3CR-F Series.

BrandOmron
ProductTimers
Model NumberH3CR-FN AC100-240/DC100-125

Omron H3CR-FN AC100-240/DC100-125 Timer - Technical Specifications

SpecificationValue
Rated power supply voltage100 to 240 VAC 50/60 Hz 100 to 125 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier)
Allowable voltage variable range85 to 110% of the power supply voltage
Power ConsumptionApprox. 10 VA (at 240 VAC) Approx. 2.1 W (at 240 VAC)
Operation Start Voltage10% max. of rated supply voltage
Number of Times Ranges18
Opeation ModeFlicker OFF start
Control Output TypeTime-limit: DPDT
Control output (Contact output)Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Operating resettingTime-limit operation/Time-limit reset or Self-reset
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Ambient humidity rangeOperating: 35 to 85%
Accuracy of operating timeΒ±0.2% FS max. Β±0.2% Β±10 ms in a range of 1.2 s and 3 s
Setting errorΒ±5% FS Β±50 ms max.
Influence of voltageΒ±0.2% FS max. Β±0.2% Β±10 ms in a range of 1.2 s and 3 s
Influence of temperatureΒ±1% FS max. (Β±1% Β±10 ms in a range of 1.2 s and 3 s)
Insulation resistance100 MΞ© min. (at 500 VDC)
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV
Noise immunityΒ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 Β΅s, 1-ns rise)
Static immunityMulfunction: 8 kV, Destruction: 15 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 980 m/s2, 3 times each in 6 directions Malfunction: 98 m/s2, 3 times each in 6 directions
Life expectancy (relay output)Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h) Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Degree of protectionIP40 (panel surface)
Connecting method11-pin round socket
WeightApprox. 100 g

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.