+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Delta DRM-24V960W1PN 40A 960W DIN Rail Power Supply

The Delta DRM-24V960W1PN is a high-performance 40A 960W DIN Rail Power Supply designed for industrial automation systems requiring dependable 24V DC output. Delivering 40A current with 960W output power, this model ensures reliable operation for factory control panels, process equipment, and automation devices. It operates over a nominal input voltage of 100–240Vac with an extended range of 85–264Vac and supports frequencies from 50–60Hz, extended to 47–63Hz for robust industrial performance. Manufactured by Delta industrial automation products, this power supply is part of Delta power supply solutions and belongs to the DIN Rail CliQ M Series, offering compact, reliable, and efficient DC power for demanding industrial environments.

BrandDelta
Product TypeSMPS
ProductDRM-24V960W1PN

Delta40A 960W DIN Rail Power Supply DRM-24V960W1PN Technical Specifications:

SpecificationValue
Output Current40A
Output Voltage24V
Output Voltage Adjustment Range24-28Vdc
Output Power960W
Line Regulation10mV Max. (@ 85-264Vac input, 100% load)
Load Regulation50mV Max. (@ single mode, 0-100% load) 1000mV Typ. (@ parallel mode, 0-100% load)
PARD100mVpp Max.
Start-up Time800ms Max. @ 100Vac & 120Vac & 230Vac
Hold-up Time24ms Typ. @ 100Vac & 120Vac & 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 5% @ 0.7-40A load Slew rate 0.1A/µs (@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle)
Start-up with Capacitive Loads40,000µF Max.
Rise Time75ms Max. @ 100Vac & 120Vac & 230Vac (0µF, 24V, 40A) 75ms Max. @ 100Vac & 120Vac & 230Vac (40,000µF, 24V, 40A)
Power Boost Duration5 seconds Typ. 7 seconds Max.
Power Boost Recovery Time17 seconds Typ.
Nominal Input Voltage100-240Vac
Input Voltage Range85-264Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
Nominal DC Input Voltage-
DC Input Voltage Range-
Input Current10.50A Typ. @ 100Vac, 8.60A Typ. @ 120Vac, 4.50A Typ. @ 230Vac
Efficiency at 100% load94.10% Typ. @ 100Vac, 94.71% Typ. @ 120Vac, 95.98% Typ. @ 230Vac
Inrush Current11A Max. @ 100Vac, 13A Max. @ 120Vac, 20A Max. @ 230Vac
Power Factor at 100% load0.99 Typ. @ 100Vac, 0.99 Typ. @ 120Vac, 0.96 Typ. @ 230Vac
Leakage Current(Enclosure to Neutral) 0.50mA / 1.21mA @ 110Vac, 50Hz, TN/TT system / IT system 0.71mA / 1.73mA @ 132Vac, 50Hz, TN/TT system / IT system 1.18mA / 2.82mA @ 264Vac, 50Hz, TN/TT system / IT system
Power Dissipation0% load: 5.58W Typ. @ 100Vac, 4.61W Typ. @ 120Vac, 3.70W Typ. @ 230Vac 13.9W Max. @ 100Vac, 13.1W Max. @ 120Vac, 13.2W Max. @ 230Vac 100% load: 60.32W Typ. @ 100Vac, 53.71W Typ. @ 120Vac, 40.21W Typ. @ 230Vac 70.00W Max. @ 100Vac, 65.60W Max. @ 120Vac, 54.80W Max. @ 230Vac
Case Chassis / CoverAluminium
IndicatorGreen LED (DC OK) and Red LED (Overload)
Cooling SystemConvection
Input Terminal3 Pins (Rated 600V/35A)
Output Terminal4 Pins (Rated 300V/65A)
Noise Sound Pressure Level (SPL)< 25dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715
WireInput: AWG 14-8 Output: AWG: 10-6 Signal: AWG 20-16
Unit Weight2.87 kg (6.33 lb)
Operating Temperature-25°C to +70°C (Cold start -40°C)
Storage Temperature-40°C to +85°C
Power De-ratingVertical Mounting: Temperature: > 60°C de-rate power by 2.5% / °C Input Voltage: If < 90Vac, > 55°C de-rate power by 1.67% / °C Horizontal Mounting: Temperature: > 40°C de-rate power by 1.67% / °C Input Voltage: If < 90Vac, > 35°C de-rate power by 1.43% / °C
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
Vibration (Non-Operating)IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
Operating Altitude0 to 5,000 Meters (16,400 ft.) 0 to 2,500 Meters (8,200 ft.) for IEC/EN 61558
Pollution Degree2
Bump Test (Operating)IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
Over Voltage CategoryIII According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Signal Terminal5 Pins (Rated 300V/10A)

The Delta DRM-24V960W1PN 40A 960W DIN Rail Power Supply is commonly integrated into industrial control cabinets, automation panels, and high-current process equipment requiring precise 24V DC power. Its 40A output ensures consistent performance across multiple devices while the 960W power rating allows operation under high load conditions. The compact DIN rail design enables organized installation, simplifies wiring, and provides secure connections, enhancing operational efficiency in industrial automation setups.

Engineered for harsh environments, this DIN Rail power supply operates in temperatures ranging from -25°C to +70°C, with cold start capability down to -40°C and storage support up to +85°C. Input and output terminals are designed for high-current loads, with 3 pins rated at 600V/35A and 4 pins rated at 300V/65A, ensuring safe and reliable connections. Visual monitoring is made easy with green DC OK and red overload LEDs, providing immediate feedback on the operational status, helping prevent downtime in critical industrial systems.

For engineers and automation integrators seeking a high-capacity and dependable solution, the Delta DRM-24V960W1PN 40A 960W DIN Rail Power Supply delivers stable DC conversion, efficient energy management, and long-term operational reliability. Request a quote today to secure competitive pricing and dedicated technical support, ensuring uninterrupted power delivery for your industrial equipment and automation systems with this robust and reliable DIN Rail solution.

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.