| Number of inputs | 1 |
| Measurement error/uncertainty | > 500 kΩ (30 V); > 4 MΩ (others); 150 Ω (current) |
| Input filter limit frequency | 3 kHz |
| Dielectric strength | max. 36 V |
| Measuring range, nominal | ±30/10/5/2.5/1.25 V, ±640/320/160/80/40/20/10/5 mV, 0â¦5/10 V, ±20 mA, 0/4â¦20 mA, NAMUR NE43, 0â¦5 kΩ, RTD, Pt100/Pt1000, Ni, KTY, ¼ bridge (350 Ω + 120 Ω), ½ bridge (±16 mV/V), full bridge (±32 mV/V), potentiometer ⥠1 kΩ |
| Measuring range, technical | generally 107% of the nominal measuring range, see documentation |
| Measurement error/uncertainty 2 | typ. ±0.01% relative to the respective full scale value @ 23°C in some measuring ranges, see documentation |
| Housing - Design form | compact terminal housing with signal LEDs |
| Housing - Material | polycarbonate |
| Housing - Dimensions (W x H x D) | 12Â mm x 100Â mm x 68 mm |
| Housing - Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Housing - Side by side mounting by means of | double slot and key connection |
| Housing - Marking | labeling of the BZxxxx series |
| Housing - Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Housing - Connection cross-section | s*: 0.08..2.5 mm²,st*: 0.08...2.5 mm²,f*: 0.14..1.5 mm² |
| Housing - Connection cross-section AWG | s*: AWG28..14,st*: AWG28..14,f*: AWG26...16 |
| Housing - Stripping length | 8…9 mm |
| Housing - Current load power contacts | Imax: 10 A |
| Power supply | via the E-bus |
| Distributed clocks | yes |
| Distributed clock precision | << 1 µs |
| Conversion time | 100 µs/10 ksps |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 260 mA |
| Configuration | no address or configuration setting |
| Special features | integr. power supply for strain gauge 0.5â¦5 V, parameterizable, ExtendedRange 107%, free numeric filter, TrueRMS, integrator/differentiator, non-linear scaling, PeakHold |
| Weight | approx. 65Â g |
| Operating temperature | 0...55°C |
| Storage temperature | -25...+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx |
| Oversampling factor | n = 1â¦64 |
| Ex marking | ATEX:II 3 G Ex ec IIC T4 GcIECEx:Ex ec IIC T4 Gc |