During technical comparisons, EL3453-0100 appears alongside Beckhoff El9410, El9550 Beckhoff and Beckhoff El2809 so engineers assess signal types, ingress protection, and ambient tolerances accurately.
EL3453-0100 - Beckhoff EtherCAT Terminal Analog Input
Technical Specifications of Beckhoff EtherCAT Terminal Analog Input EL3453-0100:

| Brand | Beckhoff |
| Product Type | EtherCAT Terminal Analog Input |
| Product | EL3453-0100 |
EL3453-0100 Beckhoff EtherCAT Terminal Analog Input Technical Specifications
| Specification | Value |
|---|---|
| Number of inputs | 4 x current, 3 x voltage |
| Measurement error/uncertainty 2 | 0.3% relative to full scale value (U/I), 0.6% calculated value (see documentation) |
| Housing - Design form | compact terminal housing with signal LEDs |
| Housing - Material | polycarbonate |
| Housing - Dimensions (W x H x D) | 24Â mm x 100Â mm x 68 mm |
| Housing - Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Housing - Side by side mounting by means of | double slot and key connection |
| Housing - Marking | labeling of the BZxxxx series |
| Housing - Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Housing - Connection cross-section | s*: 0.08..2.5 mm²,st*: 0.08...2.5 mm²,f*: 0.14..1.5 mm² |
| Housing - Connection cross-section AWG | s*: AWG28..14,st*: AWG28..14,f*: AWG26...16 |
| Housing - Stripping length | 8…9 mm |
| Housing - Current load power contacts | Imax: 10 A |
| Distributed clocks | optional |
| Electrical isolation | 4500 V |
| Current consumption E-bus | typ. 260 mA |
| Special features | mains monitoring, precise detection of zero voltage and zero current crossing, optional single-phase operation |
| Operating temperature | 0â¦55°C |
| Storage temperature | -25â¦+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL |
| Measuring current | adjustable, 100 mA AC, 1 A AC (default), 5 A AC; potential-free |
| Measuring voltage | max. 130Â VÂ AC for voltage transformer |
| Update time | net-synchronous |
| Update interval | half mains period (10Â ms at 50Â Hz) |