| Number of inputs | 5 |
| Ground reference (input) | single-ended |
| Measurement error/uncertainty | >> 100 kΩ to wiper connection |
| Input filter limit frequency | typ. -3 dB at 3 kHz and potentiometer 50 kΩ |
| Measurement error/uncertainty 2 | < ±0.5% (relative to full scale value) |
| Housing - Design form | HD (High Density) housing with signal LEDs |
| Housing - Material | polycarbonate |
| Housing - Dimensions (W x H x D) | 12Â mm x 100Â mm x 68 mm |
| Housing - Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Housing - Side by side mounting by means of | double slot and key connection |
| Housing - Marking | labeling of the BZxxxx series |
| Housing - Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
| Housing - Connection cross-section | s*: 0.08..2.5 mm²,st*: 0.08...2.5 mm²,f*: 0.14..1.5 mm² |
| Housing - Connection cross-section AWG | s*: AWG28..14,st*: AWG28..14,f*: AWG26...16 |
| Housing - Stripping length | 8…9 mm |
| Housing - Current load power contacts | Imax: 10 A |
| Power supply | via power contacts |
| Conversion time | typ. 300â¦700 µs, dependent on settings, default setting: approx. 500 µs (5 channels, filter deactivated) |
| Electrical isolation | 500 V (E-bus/field potential) |
| Current consumption E-bus | typ. 80 mA |
| Bit width in the process image | 5 x 16 bit input |
| Configuration | no address setting, configuration via the controller |
| Special features | open-circuit recognition, supply monitoring, activatable filters, simultaneous measurement of the channels |
| Weight | approx. 70 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx |
| Current consumption power contacts | dependent on the potentiometers, max. 70 mA |
| Ex marking | ATEX:II 3 G Ex ec IIC T4 GcIECEx:Ex ec IIC T4 Gc |
| Sensor types | potentiometer 300 Ωâ¦50 kΩ |
| Measuring range | potentiometer 300 Ωâ¦50 kΩ |
| Feed voltage potentiometer | typ. 10 V ±10% |
| Output current | max. 0.3 A total supply current for the potentiometers |
| Wiring fail indication | yes |