During technical comparisons, EL3062 appears alongside Beckhoff El9410, El9550 Beckhoff and Beckhoff El2809 so engineers assess signal types, ingress protection, and ambient tolerances accurately.
EL3062 - Beckhoff EtherCAT Terminal Analog Input
Technical Specifications of Beckhoff EtherCAT Terminal Analog Input EL3062:

| Brand | Beckhoff |
| Product Type | EtherCAT Terminal Analog Input |
| Product | EL3062 |
EL3062 Beckhoff EtherCAT Terminal Analog Input Technical Specifications
| Specification | Value |
|---|---|
| Number of inputs | 2 (single-ended) |
| Measurement error/uncertainty | > 130 kΩ |
| Input filter limit frequency | 1 kHz |
| Dielectric strength | max. 30 V |
| Measurement error/uncertainty 2 | < ±0.3% (relative to full scale value) |
| Housing - Design form | compact terminal housing with signal LEDs |
| Housing - Material | polycarbonate |
| Housing - Dimensions (W x H x D) | 12Â mm x 100Â mm x 68 mm |
| Housing - Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Housing - Side by side mounting by means of | double slot and key connection |
| Housing - Marking | labeling of the BZxxxx series |
| Housing - Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Housing - Connection cross-section | s*: 0.0..2.5 mm²,st*: 0.08..2.5 mm²,f*: 0.14...1.5 mm² |
| Housing - Connection cross-section AWG | s*: AWG28...14,st*: AWG28...14,f*: AWG26...16 |
| Housing - Stripping length | 8…9 mm |
| Housing - Current load power contacts | Imax: 10 A |
| Power supply | via the E-bus |
| Conversion time | 0.625 ms default setting, configurable, multiplex |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 130 mA |
| Bit width in the process image | inputs: 8 byte |
| Special features | activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, ATEX, IECEx |
| Ex marking | ATEX:II 3 G Ex ec IIC T4 GcIECEx:Ex ec IIC T4 Gc |
| Pluggable wiring | for all ESxxxx terminals |
The Beckhoff EL3062 EtherCAT Terminal Analog Input provides two single-ended input channels designed for accurate signal acquisition in demanding automation environments. Supporting a wide measuring range with an input filter limit frequency of 1 kHz, it ensures stable and precise measurements with a typical error of less than ±0.3% full scale. Its fast 0.625 ms conversion time, configurable through multiplexing, makes it suitable for high-speed process monitoring.
Engineered for reliability, the EL3062 features 500 V electrical isolation between E-bus and signal voltage, ensuring safe integration into complex systems. It is optimized with FIR/IIR filters and limit value monitoring, providing engineers with advanced diagnostic capabilities and better control over input signals. The terminal operates directly via the E-bus power supply, consuming only 130 mA, and is designed in a compact 12 mm housing with clear signal LEDs for diagnostics. Its rugged design supports operating temperatures from -25°C to +60°C, vibration resistance, and EMC compliance, making it ideal for long-term deployment in industrial plants.
Applications of the EL3062 EtherCAT Terminal Analog Input include machine automation, energy management, process industries, and factory monitoring where accurate current and voltage measurement is critical. Maintenance engineers benefit from its plug-and-play setup without complex configuration, while advanced users appreciate its precision filters and limit monitoring for optimizing production lines. Certified with CE, CCC, ATEX, and IECEx approvals, this terminal is trusted worldwide for its durability, compliance, and accuracy—delivering dependable performance for modern automation needs.