Many procurement teams check FLEXTOP-2222 against Baumer Proximity Sensor, Baumer Te2 and Baumer Industrial Cameras before signing purchase orders, verifying quality, compliance, and after-sales support availability.
Baumer FlexTop 2222 Temperature Measurement
The Baumer FlexTop 2222 Temperature Measurement offers a 0 … 60 s, 4 … 20 mA , 2-wire, 20 … 4 mA , 2-wire, and power supply. Manufactured by Baumer under the Baumer Temperature Measurement category, this model belongs to the VS Series.

| Brand | Baumer |
| Product Type | Temperature Measurement |
| Model Number | FlexTop 2222 |
Baumer FlexTop 2222 Temperature Measurement – Technical Specifications
| Specification | Value |
|---|---|
| Degree of protection (EN 60529) | IP 55 |
| Humidity | < 98 % RH , condensing |
| Damping | 0 … 60 s |
| Output signal | 4 … 20 mA , 2-wire, 20 … 4 mA , 2-wire |
| Accuracy | < 0.025 % FSR |
| Temperature drift | ± 0.01 %/K , max. |
| Load resistance | Rs ≤ (V DC - 7 V)/0.023 A |
| Resolution | 14 bit |
| Up/Down scaling limits | 23 mA / 3.5 mA |
| Ripple immunity | < 1 % FSR (1 Vrms, 50Hz...1kHz) |
| Effect of variations in supply voltage | 0.001 %/V |
| EMC | EN 61326-1, DNV GL - Class A, EN 50121-3-2:2016 |
| Namur | NE21 |
| Explosion protection | ATEX II 1 G Ex ia IIC T6...T4, ATEX II 3 G Ex ec IIC T6...T5 Gc, IECEx Ex ia IIC T6...T4, IECEx Ex ec IIC T6...T5 Gc |
| Characteristic | Linear or customised with max. 30 points |
| Step response time, T90 | < 450 ms |
| Properties | Read serial number, Read/Change user ID, Read/Change configuration, Read input signal value, Read output signal value, Input signal logging, 2-point sensor-trim, For more information please see ‚HART Field Device Specification‘ |
| Protocol | HCF standard, Rev.7, including „Temperature Device Family“ commands |
Ask for the Pricing of Baumer Temperature Measurement FlexTop 2222 at unbeatable prices. Detailed Specifications of FlexTop 2222, feature transmitter is rated IP 55 for protection and operates efficiently in humidity levels below < 98 % RH , condensing. It meets 14 bit Resolution. Built to withstand industrial conditions, it endures Up/Down scaling limits of 23 mA / 3.5 mA, with a Ripple immunity < 1 % FSR (1 Vrms, 50Hz...1kHz) standards. The damping is 0 … 60 s, providing precise control. The output signal is an 4 … 20 mA , 2-wire, 20 … 4 mA , 2-wire configuration, ensuring stable and accurate transmission. With an accuracy of < 0.025 % FSR and temperature drift of ± 0.01 %/K , max., it maintains exceptional precision. The load resistance follows Rs ≤ (V DC - 7 V)/0.023 A for optimal operation. Now's the Time to Secure a Quote for your requirement of Temperature Measurement. We're committed to offering more favorable pricing and more responsive support than other Traders.