Delta DVP04PT-H2 Programmable Logic Controller
The Delta DVP04PT-H2 Programmable Logic Controller (PLC) is a high-accuracy Analog Module designed for precise temperature measurement in industrial systems. It supports 4 points of platinum RTD input, including Pt100, Pt1000, Ni100, Ni1000, with 0โ300ฮฉ / 0โ3000ฮฉ resistance input capability and a fine 0.1ยฐC resolution. With a built-in RS-485 interface, it ensures stable communication and seamless integration into process-control environments requiring dependable sensor monitoring. Manufactured by Delta, part of the Delta Programmable Logic Controller lineup, this module belongs to the Delta DVP-EH3 Series.
| Brand | Delta |
| Product Type | Programmable Logic Controller |
| Model Number | DVP04PT-H2 |
Delta DVP04PT-H2 Programmable Logic Controller - Technical Specifications
| Specification | Value |
|---|---|
| Built-in | RS-485 interface |
| Power Supply Voltage | 24VDC (-15%~20%) |
| Resolution | 0.1ยบC |
| Analog I/O Modules | 4 points of platinum RTD (Pt100, Pt1000, Ni100, Ni1000) sensor input *1 / 0~300ฮฉ or 0~3000ฮฉ resistance input |
| Fuse capacity | ES: 2A/ 250VAC; SV: 2.5A/ 30VDC |
| Power Consumption | 2.5 W |
| Spike Voltage Durability | 1500VAC (Primary-secondary); 1500VAC (Primary-PE); 500VAC (Secondary-PE) |
| Insulation Impedance | >5 Mฮฉ (all I/O point-to-ground: 500VDC) |
| Noise Immunity | ESD: 8 kV Air Discharge EFT: Power Line, 2 kV Digital I/O: 1 kV Analog & Communication I/O: 1 kV RS: 26 MHz~1GHz, 10V/m |
| Earth | The diameter of grounding wire shall not be shorter than that of the power supply cable. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.) |
| Storagr Operation Temperature | Storage: -25ยบC ~70ยบC (temperature) Operation: 0ยบC ~55ยบC (temperature) |
| Storage Operation Humidity | Storage: -25ยบC ~70ยบC (temperature) Operation: 0ยบC ~55ยบC (temperature) |
| Response Time | 200ms |
| Input Signal Voltage | 24VDC ยฑ10% (5 mA) |
Mail Us for Delta PLC RTD Module DVP04PT-H2 at the lowest pricing. Technical Specs Summary of DVP04PT-H2 includes, 4 points of platinum RTD (Pt100, Pt1000, Ni100, Ni1000) sensor input *1 / 0~300ฮฉ or 0~3000ฮฉ resistance input, Resolution: 0.1ยบC, Built-in RS-485 interface. And It Delivers {3-5 Technical Spec Points}. Capture the Best Deal with a Quote for your requirement of Delta PLC RTD Module. Our promise: More affordable pricing and more personalized support than other Dealers.