Home GIC Voltage Monitoring DM Series MA51BK GIC MA51BK Voltage Monitoring The GIC MA51BK Voltage Monitoring offers 415 VAC supply voltage, 1 C/O relay output, Base / DIN rail mounting, IP 20 for Terminals, IP 40 for Enclosure degree of protection. Manufactured by GIC under the GIC Voltage Monitoring category, this model belongs to the GIC DM Series .
Brand GIC Product Type Voltage Monitoring Model Number MA51BK
GIC MA51BK Voltage Monitoring – Technical Specifications Specification Value Supply Voltage 415 VAC Frequency 50/60 Hz Power Consumption (Max.) 15 VA Phase Loss Yes Phase Asymmetry 40 V (± 10 V) Hysterisis 10 to 18 V ON Delay 2 s (± 2 s) Trip Time (OFF Delay) 7 s (± 2 s) Relay Output 1 C/O Contact Rating 5A (For ‘NO’) & 3A (For ‘NC’) @ 250 VAC / 28 VDC (Resistive) Electrical Life 1X10^ 5 Mechanical Life 3X10^ 6 Utilization Category AC-15 Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A Utilization Category DC-13 Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A Operating Temperature - 15 C to + 50 C Storage Temperature - 20 C to + 65 C Humidity (Non Condensing) 95% (Rh) Enclosure Flame Retardant UL 94-V0 Dimension (W x H x D) (in mm) 36 X 60 X 90 Weight 120 g Mounting Base / DIN rail Degree of Protection IP 20 for Terminals, IP 40 for Enclosure