BC9191 Beckhoff Bus Terminal Controllers Technical Specifications

BrandBeckhoff
Product TypeBus Terminal Controllers
ProductBC9191

BC9191 Beckhoff Bus Terminal Controllers Technical Specifications

SpecificationValue
Programmingwith TwinCAT 2 via Ethernet
Program memory48 kbytes
Data memory32 kbytes
Remanent data2 kbytes
Runtime system1 PLC task
Programming languagesIEC 61131-3 (IL, LD, FBD, SFC, ST)
Number of Bus Terminals64
Max. number of bytes fieldbus512 byte input and 512 byte output
Bus interface2 x RJ45 (switched)
Current supply K-bus200 mA
Weightapprox. 345 g
Operating temperature0...55°C
Storage temperature-25...+85°C
Protect. rating/installation pos.IP20/vertical
Approvals/markingsCE
ProtocolTwinCAT ADS, Modbus TCP
Ethernet interface2 x RJ45 (switched)
Digital inputs3 contacts (e.g. window contact, dew point, occupancy sensor)
Analog inputs3 x 0…10 V (e.g. CO2sensor, air quality sensor, brightness sensor)1 x PT/Ni1000 (-20…+60 °C) for air temperature measurement1 x resistance measurement for set value specification (0…10 KΩ)
Digital outputs1 x 10Â mA, LED output (max. 24Â V)1 x 230 V AC, 10 A, relay (e.g. air heater)3 x 230 V AC, 1 A, relay (3-stage fan)2 x 230 V AC, 1 A, triac (e.g. valves for heating and cooling)
Analog outputs2 x 0…10 V (e.g. volumetric air flow controller)
Sub bus systemconnection to KL6583 (EnOcean®)
Supply voltage230 V AC
Design formcompact controller
Materialpolycarbonate
Dimensions (W x H x D)118 mm (127 mm with end cover and DIN rail mounting) x 100 mm x 70 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Wiringspring-loaded technique with pluggable wiring level
Connection cross-sectionsee documentation
Stripping lengthsee documentation