Technical Specifications of Schneider Altivar Process ATV600 VSD ATV630D11N4Z:
Spec | Value |
---|---|
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Connection Type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Motor Power KW | 11 kW (normal duty)7.5 kW (heavy duty) |
Switching Frequency | 2...12 kHz adjustable4...12 kHz with derating factor |
Schneider Altivar Process ATV600 VSD ATV630D11N4Z Technical Specifications:
Specification | Value |
---|---|
Maximum input current | 19.8 A |
Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Motor: screw terminal 6...10 mm²/AWG 10...AWG 8Line side: screw terminal 6 mm²/AWG 10 |
Power dissipation in W | Natural convection: 51 W at 380 V, switching frequency 4 kHzForced convection: 255 W at 380 V, switching frequency 4 kHz |
Overvoltage category | III |
Net weight | 6.9 kg |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Frequency resolution | Display unit: 0.1 HzAnalog input: 0.012/50 Hz |
Output voltage | <= power supply voltage |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Product or component type | Variable speed drive |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA |
Nominal switching frequency | 4 kHz |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
Maximum transient current | 25.9 A during 60 s (normal duty)24.8 A during 60 s (heavy duty) |
Relay output number | 3 |
Type of polarization | No impedance |
Product specific application | Process and utilities |
Volume of cooling air | 103 m3/h |
Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Method of access | Slave Modbus TCP |
Product destination | Asynchronous motorsSynchronous motors |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Ambient air temperature for storage | -40…70 °C |
Motor power hp | 15 hp normal duty10 hp heavy duty |
Transmission rate | 10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Maximum THDI | <48 % from 80...100 % of load conforming to IEC 61000-3-12 |
Height | 345 mm |
Type of cooling | Forced convection |
Motor power kW | 11 kW (normal duty)7.5 kW (heavy duty) |
Number of Units in Package 1 | 1 |
Physical interface | Ethernet2-wire RS 485 |
Switching frequency | 2...12 kHz adjustable4...12 kHz with derating factor |
Apparent power | 14.1 kVA at 480 V (normal duty)10.4 kVA at 480 V (heavy duty) |
Standards | UL 508CIEC 61800-3IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1 |
Operating position | Vertical +/- 10 degree |
Discrete input logic | Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) |
Package 2 Length | 80.000 cm |
Range of product | Altivar Process ATV600 |
[Us] rated supply voltage | 380...480 V - 15...10 % |
Permissible temporary current boost | 1.1 x In during 60 s (normal duty)1.5 x In during 60 s (heavy duty) |
Marking | CE |
Analogue input number | 3 |
Asynchronous motor control profile | Constant torque standardOptimized torque modeVariable torque standard |
Enclosure mounting | With heat sink |
Isolation | Between power and control terminals |
Ambient air temperature for operation | -15…50 °C (without derating)50…60 °C (with derating factor) |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Supply frequency | 50...60 Hz - 5...5 % |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
Analogue output number | 2 |
Pollution degree | 2 |
Get A Quote for Schneider Altivar Process ATV600 VSD ATV630D11N4Z at the best price. Here are the brief Technical Specifications of ATV630D11N4Z are Altivar Process ATV600 range, designed for Process and utilities applications. It has a maximum input current of 19.8 A, with a frequency resolution of Display unit: 0.1 HzAnalog input: 0.012/50 Hz. The output voltage is equal to or less than the <= power supply voltage, while the maximum transient current reaches 25.9 A during 60 s (normal duty)24.8 A during 60 s (heavy duty) operations. The sensor features a motor power of 15 hp normal duty10 hp heavy duty. Its height is 345 mm, and the physical interface includes Ethernet2-wire RS 485. The switching frequency is 2...12 kHz adjustable4...12 kHz with derating factor. It operates at a rated supply voltage [Us] of 380...480 V - 15...10 % with a supply frequency of 50...60 Hz - 5...5 %. The maximum output frequency is 500 kHz, with a Cabinet mount mode for secure installation. It's Time to get a Quote for your requirement of Schneider Altivar Process ATV600 VSD. We guarantee unmatched pricing and unparalleled support compared to other Distributors.