+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Omron S8FS-C20024D Power Supply

Omron S8FS-C20024D SMPS is a 200 W switch mode power supply designed around a 24 VDC output with 8.8 A rated current. It uses single-phase input, DIN rail mounting, screw terminals, and terminal blocks for control-panel power distribution. Efficiency is 88% typical at both 115 VAC and 230 VAC input. The supported supply ranges are 90 to 132 VAC, 180 to 264 VAC, and 254 to 373 VDC at 50/60 Hz. Within the S8FS-C Series, the S8FS-C20024D provides a DIN rail 200 W, 24 VDC configuration. Compare other 24V SMPS models from Omron machine control products.

Omron S8FS-C20024D Power Supply
BrandOmron
ProductPower Supply
Model NumberS8FS-C20024D

Omron S8FS-C20024D Power Supply - Technical Specifications

SpecificationValue
Power rating200 W
Output voltage24 VDC
Rated output current8.8 A
Terminal typeScrew Terminal
Mounting methodDIN rail
ConnectionTerminal blocks
Efficiency88 % typ.(at 115 VAC input) 88 % typ.(at 230 VAC input)
Rated input voltageSingle phase 90 to 132 VAC , Single phase 180 to 264 VAC , 254 to 373 VDC
Rated input current4 A typ.(at 115 VAC input) 2.3 A typ.(at 230 VAC input)
Input Leakage current0.40 A typ.(at 115 VAC input) 0.75 A typ.(at 230 VAC input)
Input Frequency50/60 Hz
Output indicatorYes (color: green)
Output voltage variable range-10% to 10% (with V. ADJ)
Start-up time580 ms max.(at 115 VAC input) 550 ms max.(at 230 VAC input)
Hold time38 ms max.(at 115 VAC input) 45 ms max.(at 230 VAC input)
Vibration resistance10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions 10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Ambient temperature (Operating)-20 to 50°C
Ambient temperature (Storage)-40 to 85°C
Ambient humidity (OperatingStorage)20% to 90% (Storage humidity: 10% to 95%)
Cooling fanNo
Weight700 g max.

The Omron S8FS-C20024D Power Supply provides 200 W rated power with a 24 VDC output and 8.8 A rated current. It uses single-phase input, DIN rail mounting, screw terminals, and terminal blocks for electrical-panel installation. Efficiency is 88% typical at both 115 VAC and 230 VAC input. Supported supply ranges include 90 to 132 VAC, 180 to 264 VAC, and 254 to 373 VDC at 50/60 Hz. A green output indicator provides status visibility, while V.ADJ allows adjustment from -10% to 10%. Startup time is 580 ms maximum at 115 VAC and 550 ms maximum at 230 VAC. The fanless unit operates from -20 to 50°C and weighs up to 700 g.

The connected equipment should operate from 24 VDC and remain within the 8.8 A current limit. DIN rail space, terminal accessibility, incoming voltage, and ambient conditions should all be verified independently. A model with a different output voltage represents a different load relationship even when it belongs to the same broader product family. For comparison with a 100 W DIN rail configuration delivering 48 VDC at 2.3 A, see the Omron S8FS-C10048.