+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Omron S8FS-C20005J Power Supply

Omron S8FS-C20005J SMPS is a 200 W switch mode power supply configured to provide 5 VDC for high-current industrial control loads. It delivers 40 A rated output current and uses single-phase input, DIN rail mounting, and screw terminals for panel installation. Efficiency is 81% typical at both 115 VAC and 230 VAC input. Supported input ranges are 90 to 132 VAC, 180 to 264 VAC, and 254 to 373 VDC at 50/60 Hz. Within the S8FS-C Series, the S8FS-C20005J provides a DIN rail 200 W, 5 VDC configuration. Compare other 200W 5V power supplies from Omron automation solutions.

Omron S8FS-C20005J Power Supply
BrandOmron
ProductPower Supply
Model NumberS8FS-C20005J

Omron S8FS-C20005J Power Supply - Technical Specifications

SpecificationValue
Power rating200 W
Output voltage5 VDC
Rated output current40 A
Terminal typeScrew Terminal
Mounting methodDIN rail
ConnectionTerminal blocks
Efficiency81 % typ.(at 115 VAC input) 81 % typ.(at 230 VAC input)
Rated input voltageSingle phase 90 to 132 VAC , Single phase 180 to 264 VAC , 254 to 373 VDC
Rated input current4 A typ.(at 115 VAC input) 2.3 A typ.(at 230 VAC input)
Input Leakage current0.35 A typ.(at 115 VAC input) 0.60 A typ.(at 230 VAC input)
Input Frequency50/60 Hz
Output indicatorYes (color: green)
Output voltage variable range-10% to 10% (with V. ADJ)
Start-up time620 ms max.(at 115 VAC input) 600 ms max.(at 230 VAC input)
Hold time32 ms max.(at 115 VAC input) 37 ms max.(at 230 VAC input)
Vibration resistance10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z directions 10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z directions
Shock resistance150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Ambient temperature (Operating)-20 to 50°C
Ambient temperature (Storage)-40 to 85°C
Ambient humidity (OperatingStorage)20% to 90% (Storage humidity: 10% to 95%)
Cooling fanNo
Weight700 g max.

The Omron S8FS-C20005J Power Supply provides 200 W rated power with a 5 VDC output and 40 A rated current, creating a low-voltage, high-current configuration. It uses single-phase input, DIN rail mounting, screw terminals, and terminal blocks for panel installation. Efficiency is 81% typical at both 115 VAC and 230 VAC input. Supported incoming ranges are 90 to 132 VAC, 180 to 264 VAC, and 254 to 373 VDC at 50/60 Hz. A green output indicator provides operating status, while V.ADJ allows -10% to 10% adjustment. The fanless unit operates from -20 to 50°C, stores from -40 to 85°C, and weighs up to 700 g. These specifications make output current and thermal limits important selection factors.

The connected load must specifically require 5 VDC and keep combined demand within the 40 A rating. DIN rail space, terminal access, and conductor requirements should be evaluated together with incoming supply conditions. A higher-current comparison is most meaningful when the nominal output remains at 5 VDC. For a 350 W configuration that maintains the same 5 VDC output while increasing rated current to 60 A, compare the Omron S8FS-C35005.