+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Omron NJ-PD3001 Machine Automation Controller

The Omron NJ-PD3001 Machine Automation Controller Power Supply Unit is designed for compatible NJ-Series controller systems operating from a 24 VDC supply. It provides the system power required by supported NJ CPUs and expansion units, including the controller-side power functions described for the DC-powered configuration. This allows control, I/O, and communication units within the compatible NJ architecture to receive operating power from the system power supply. The NJ-PD3001 provides a DC-input power option for NJ controller installations. Its system-power function complements the DC-input PLC power supply range within Omron industrial automation systems.

Omron NJ-PD3001 Machine Automation Controllers
BrandOmron
Product TypeMachine Automation Controllers
Model NumberNJ-PD3001

Omron NJ-PD3001 Machine Automation Controller - Technical Specifications

SpecificationValue
Product nameDC Power Supply Unit
Supply voltage24 VDC
Operating voltage and frequency ranges19.2 to 28.8 VDC
Power Consumption60 W max.
Inrush CurrentAt 24 VDC: 30 A/20 ms max. for cold start
Output capacity5 VDC, 6.0 A (including supply to CPU Unit using CPU Rack) 5 VDC, 6.0 A (using Expansion Rack) 24 VDC, 1.0 A Total: 30 W max.
RUN OutputContact configuration: SPST-NO Switch capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load)
Insulation Resistance20 MΩ min. (at 500 VDC) between DC external and GR terminals
Dielectric Strength1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals Leakage current: 10 mA max.
Noise immunity2 kV on power supply line (Conforms to IEC 61000-4-4.)
Vibration resistance5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 100 min (Time coefficient: 10 min × coefficient factor 10 = total time 100 min) (according to IEC 60068-2-6)
Shock resistance147 m/s2 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s2) (according to IEC 60068-2-27)
Ambient operating temperature0 to 55°C
Ambient operating humidity10% to 90% (with no condensation)
AtmosphereMust be free from corrosive gases.
Ambient storage temperature-20 to 75°C
GroundingLess than 100 Ω
EnclosureMounted in panel
Weight490 g max