| Shape | 1/16 DIN 48 × 48 × 78 (W × H × D) |
| Power supply voltage | 100 to 240 VAC, 50/60 Hz |
| Operating voltage range/ Allowable voltage variable range | 85 to 110% of the power supply voltage |
| Power consumption | 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA)
24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) |
| Control method | ON/OFF or 2-PID control with auto-tuning |
| Input Type/Temperature input | Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V |
| Control output 1 | Relay output |
| Number of total auxiliary output | 2 |
| Setting method | Digital setting using front panel keys |
| Indication method | 11-segment digital display and individual indicators (7-segments displays also possible); Character height: PV: 11 mm, SV: 6.5 mm |
| Insulation resistance | 20 MΩ min. (at 500 VDC) |
| Dielectric strength | 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) |
| Vibration resistance | Malfunction: 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions |
| Shock resistance | Malfunction: 100 m/s2, 3 times each in X, Y, and Z directions
Destruction: 300 m/s2, 3 times each in X, Y, and Z directions |
| Ambient temperature (Operating) | −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C |
| Ambient temperature (Storage) | −25 to 65°C (with no condensation or icing) |
| Ambient humidity (Operating) | 25% to 85% |
| Degree of protection | Front panel: IP66, Rear case: IP20, Terminals: IP00 |
| Case color | Black |
| Terminal type | Screw terminal blocks |
| Weight | Controller: Approx. 210 g, Adapter: Approx. 4 g × 2 |