+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

IP6022-B518 - Beckhoff Fieldbus Box And IO-Link Box

Technical Specifications of Beckhoff Fieldbus Box And IO-Link Box IP6022-B518:

Beckhoff IP6022-B518
BrandBeckhoff
Product TypeFieldbus Box And IO-Link Box
ProductIP6022-B518

IP6022-B518 Beckhoff Fieldbus Box And IO-Link Box Technical Specifications

SpecificationValue
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Bit width in the process imageinput/output: 3 x 8Â bit user data, 1 x 8Â bit control/status (up to 5 x 8Â bit user data are possible)
Electrical isolationRS485/control voltage: 500 V, to the fieldbus: depends on the bus system
Digital peripheral signalsaccording to I/O type
Analog peripheral signalsaccording to I/O type
Configuration possibilitythrough KS2000 or the controller (service data objects)
Data transfer ratesautomatic detection of 10 kbaud up to 1Â Mbaud
Bus interface1 x M12 plug, 5-pin, 1 x M12 socket, 5-pin (tee-connector integrated)
Data transfer mediumshielded copper cable, 2 x signal, 1 x CAN ground (recommended)
Power supplycontrol voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type
Box supply current45 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current 1according to I/O type
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing - Dimensions (W x H x D)30 mm x 210 mm x 26.5 mm
Housing - MaterialPA6 (polyamide)
Housing - Installation2 fixing holes 3.5 mm diameter for M3
Common-mode voltage UCMmax. -7…+12 V to ground
Nominal voltage24 V DC (-15%/+20%)