+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

EL3174-0002 - Beckhoff EtherCAT Terminal Analog Input

Technical Specifications of Beckhoff EtherCAT Terminal Analog Input EL3174-0002:

Beckhoff EL3174-0002
BrandBeckhoff
Product TypeEtherCAT Terminal Analog Input
ProductEL3174-0002

EL3174-0002 Beckhoff EtherCAT Terminal Analog Input Technical Specifications

SpecificationValue
Number of inputs4
Measurement error/uncertainty> 200 kΩ | typ. 85 Ω
Input filter limit frequency5 kHz
Measuring range, nominal-10/0…+10 V | -20/0/+4…+20 mA
Measuring range, technical-10.73…+10.73 V | -21.47…+21.47 mA
Measurement error/uncertainty 2< ±0.2% (at 25°C ±5°C, or else < ±0.3%, relative to full scale value)
Housing - Design formcompact terminal housing with signal LEDs
Housing - Materialpolycarbonate
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.0..2.5 mm²,st*: 0.08..2.5 mm²,f*: 0.14...1.5 mm²
Housing - Connection cross-section AWGs*: AWG28...14,st*: AWG28...14,f*: AWG26...16
Housing - Stripping length8…9 mm
Housing - Current load power contactsImax: 10 A
Power supplyvia the E-bus
Distributed clocksyes
Distributed clock precision<< 1 µs
Conversion timeminimum 150 µs
Electrical isolation2500 V functional isolation (test voltage channel/channel and channel/fieldbus, production test)
Current consumption E-bustyp. 150 mA
Bit width in the process imageinputs: 16 byte
Configurationno address or configuration setting
Special featuresU/I parameterizable, ExtendedRange, standard and compact process image, activatable FIR/IIR filters
Weightapprox. 65Â g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, CCC, UL, ATEX, IECEx, cFMus
Ex markingATEX:Â Â II 3G Ex ec IIC T4 GcIECEx:Â Â Ex ec IIC T4 GccFMus:Â Â Class I, Division 2, Groups A, B, C, DÂ Â Class I, Zone 2, AEx ec IIC T4 Gc