Omron H5CZ-L8D Digital Timer

The Omron H5CZ-L8D Timer is a dependable multifunction timing solution designed for AC and DC applications requiring precision and flexibility. It offers ten selectable timing ranges, SPDT output, and an easy-to-read 4-digit LCD, making it suitable for machine panels and automation systems. With multiple start/reset modes and high noise immunity, it performs reliably even in demanding environments. Built by Omron and cataloged under Omron Timers, this model is part of the trusted Omron H5CZ Series known for accurate and stable timing performance.

BrandOmron
ProductTimers
Model NumberH5CZ-L8D

Omron H5CZ-L8D Digital Timer - Technical Specifications

SpecificationValue
Rated supply voltage24 VAC (50/60 Hz) 12 to 24 VDC (Ripple 20% max.)
Operating voltage range12 to 24 VDC: 90% to 110% of rated supply voltage 24 VAC: 85 to 110% of rated supply voltage
Connection method8-pin round socket
Mounting methodFlush mounting / Surface mounting
Power consumptionApprox. 5.1 VA/Approx. 2.4 W
Time ranges (Number of ranges)10
Time ranges0.001 to 9.999 s 0.01 to 99.99 s 0.1 to 999.9 s 1 to 9999 s 0.1 to 999.9 min 1 to 9999 min 0.1 to 999.9 h 1 to 9999 h 1 s to 99 min 59 s 1 min to 99 h 59 min
Input methodNo-voltage input
Output modesA: Signal ON delay (Ⅰ) A-1:Signal ON delay (Ⅱ) A-2: Power ON delay (Ⅰ) A-3: Power ON delay (Ⅱ) b: Repeat cycle (Ⅰ) b-1: Repeat cycle (Ⅱ) d: Signal OFF delay E: Interval F: Cumulative Z: ON/OFF-duty adjustable flicker S: Stopwatch toff: Flicker OFF start (Ⅰ) ton: Flicker ON start (Ⅰ) toff-1: Flicker OFF start (Ⅱ) ton-1: Flicker ON start (Ⅱ)
Control output (Contact output)Time-limit contact: SPDT Resistive load: 5 A at 250 VAC/30 VDC (cosφ = 1) Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Reset systemPower reset (depending on output mode)/Automatic reset (depending on output mode)/External reset/Manual reset
Timer modeElapsed time (UP) and remaining time (DOWN) (selectable)
Display methodLCD 4 digit
Character heightPresent value: 10 mm Set value: 6 mm
Ambient temperature range-10 to 55 ℃ (with no freezing or condensation) When mount timer side by side: -10 to 50 ℃ (with no freezing or condensation)
Ambient humidity (Operating)25 to 85%
Accuracy of operating timePower-ON start: ±0.01% ±0.05 s max. (The values are based on the set value.) Signal start: ±0.005% ±0.03 s max. (The values are based on the set value.)
Setting errorPower-ON start: ±0.01% ±0.05 s max. (The values are based on the set value.) Signal start: ±0.005% ±0.03 s max. (The values are based on the set value.)
Influence of voltagePower-ON start: ±0.01% ±0.05 s max. (The values are based on the set value.) Signal start: ±0.005% ±0.03 s max. (The values are based on the set value.)
Influence of temperaturePower-ON start: ±0.01% ±0.05 s max. (The values are based on the set value.) Signal start: ±0.005% ±0.03 s max. (The values are based on the set value.)
Insulation resistanceBetween current carrying terminals and exposed non-current carrying metal parts: 100 MΩ min. (at 500 VDC) Between non-continuous contacts: 100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min Between operating power circuit and input circuit: 2000 VAC 50/60 Hz 1 min Between control output, and power supply/input circuit: 2000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 1.0 kV Between current carrying terminals and exposed non-current carrying metal parts: 1.5 kV
Noise immunityBetween power terminals: ±1.5 kV Between input terminals: ±600 kV square-wave noise by noise simulator, pulse width: 100 ns/1 µs, 1-ns rise
Static immunityMulfunction: 8 kV, Destruction: 15 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz 0.35 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 300 m/s2, 3 times each in 3 axes each directions Malfunction: 100 m/s2, 3 times each in 3 axes each directions
Life expectancyElectrical: 100,000 operations min. (5 A at 250 VAC resistive load at 1800 operations/h, 23 ℃) Mechanical: 10 million operations min. (under no load at 1,800 operations/h, 23 ℃)
Degree of protectionIEC IP66, UL508 Type 4X (indoors) (when using the Y92S-29 Waterproof Packing and Y92F-30 Flush Mounting Adapter)
Case colorLight gray (Munsell 5Y7/1)
Accessory (sold separately)Soft Cover: Y92A-48F1 Hard Cover: Y92A-48 Flush mounting adapter: Y92F-30 Waterproof packing: Y92S-29
Ambient temperature range-10 to 55 ℃ (with no freezing or condensation) When mount timer side by side: -10 to 50 ℃ (with no freezing or condensation)
WeightMain Unit: Approx. 105 g
IndMALL Automation Offers Omron ICD 4 Digit Power ON Start Timer, H5CZ-L8D with exclusive offers. Component Specifications of H5CZ-L8D features 24 VAC (50/60 Hz) 12 to 24 VDC (Ripple 20% max.), 12 to 24 VDC: 90% to 110% of rated supply voltage 24 VAC: 85 to 110% of rated supply voltage, Approx. 5.1 VA/Approx. 2.4 W, 10, LCD 4 digit, Present value: 10 mm, Set value: 6 mm, Key protect Switch & Flush mounting / Surface mounting. It rounds off its features with a 25 to 85%, 8-pin round socket & Light gray (Munsell 5Y7/1). Don't Miss Out on a Quote for your requirement of Omron ICD 4 Digit Power ON Start Timer. Our competitive edge: better pricing and support than other Suppliers.

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.