| Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
| Operating voltage range | 85 to 110% of rated supply voltage |
| Control output (Contact output) | SPDT
Resistive load: 3 A at 250 VAC (cosφ=1)
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
| Connection method | 11-pin round socket |
| Mounting method | Flush mounting / Surface mounting |
| Power consumption | Approx. 12 VA (at 240 VAC)/Approx. 2.5 W (at 240 VAC) |
| Time ranges | 1 min to 99 h 59 min |
| Input method | Contact: Contact open and short-circuit input
No-contact: Open-collector transistor ON/OFF input |
| Output modes | N: Power ON delay |
| Reset system | External reset |
| Timer mode | UP display timer (increments form 0 to the set time) |
| Display method | 7-segment LED 4 digit |
| Character height | 10 mm |
| Ambient temperature range | -10 to 55 ℃ (with no icing) |
| Ambient humidity (Operating) | -25 to 65 ℃ (with no icing) |
| Accuracy of operating time | Reset start: ±0.005% ±0.03 s max. (The values are based on the set value.) |
| Setting error | Reset start: ±0.005% ±0.03 s max. (The values are based on the set value.) |
| Influence of voltage | Reset start: ±0.005% ±0.03 s max. (The values are based on the set value.) |
| Influence of temperature | Reset start: ±0.005% ±0.03 s max. (The values are based on the set value.) |
| Insulation resistance | Between current carrying terminals and exposed non-current carrying metal parts: 100 MΩ min. (at 500 VDC)
Between operating power circuit and control output circuit: 100 MΩ min. (at 500 VDC) |
| Dielectric strength | Between current carrying terminals and exposed non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min
Between operating power circuit and control output circuit: 2000 VAC 50/60 Hz 1 min |
| Impulse withstand voltage | Between operating power supply terminals: 6 kV
Between current carrying terminals and exposed non-current carrying metal parts: 6 kV |
| Noise immunity | Between operating power supply terminals: ±2 kV
Square-wave noise by noise simulator |
| Static immunity | Mulfunction: 8 kV |
| Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h
Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
| Shock resistance | Destruction: 300 m/s2, 3 times each in 6 directions
Malfunction: 100 m/s2, 3 times each in 6 directions |
| Case color | Light gray (Munsell 5Y7/1) |
| Accessory (sold separately) | Soft Cover: Y92A-48D
Hard Cover: Y92A-48B
Flush mounting adapter: Y92F-30 |
| Ambient temperature range | -10 to 55 ℃ (with no icing) |
| Ambient humidity range | 35 to 85% |
| Life expectancy (relay output) | Electrical: 100,000 operations min. (3 A at 250 VAC resistive load)
Mechanical: 10 million operations min. |
| Time ranges (Number of ranges) | 1 |
| External reset and Gate | Minimum input signal width: 0.02 s
Residual voltage: 2 V max. |
| Applicable socket | P2CF-08, P2CF-08-E, P3G-08 |
| Weight | Approx. 110 g |