+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Omron H3CR-H8RL AC/DC24 M Solid-state Timer

The Omron H3CR-H8RL AC/DC24 M Timer is built for dependable timing control with an allowable voltage variable range of 85 to 110% of the power supply voltage and an operation start voltage of 30% max. of rated supply voltage. It operates using Reset input signals with a No-voltage input method, supporting 4 time ranges for dependable performance. Designed for Power OFF-delay operation, it provides a reliable SPDT time-limit control output through an 8-pin round socket connection. Manufactured by Omron, listed under Omron Timers, and part of the Omron H3CR Series.

BrandOmron
ProductTimers
Model NumberH3CR-H8RL AC/DC24 M

Omron H3CR-H8RL AC/DC24 M Solid-state Timer - Technical Specifications

SpecificationValue
Rated power supply voltage24 VAC 50/60 Hz 24 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier)
Allowable voltage variable range85 to 110% of the power supply voltage
Number of time ranges4
Operation modePower OFF-delay
Control output (Type)Time-limit: SPDT
Control output (Contact output)Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC Minimum applicable load: 100 mA at 5 VDC (failure level: P Reference value)
Operating resettingInstantaneous operation/Time-limit reset/Forced reset
Connection method8-pin round socket
Power consumptionApprox. 0.17 VA (at 24 VAC) Approx. 0.15 W (at 24 VAC)/Approx. 1 W (at 24 VDC)
Input methodNo-voltage input
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Accuracy of operating time±0.2% FS max
Setting error±5% FS ±50 ms max.
Influence of voltage±0.2% FS max
Influence of temperature±1% FS max
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 1 kV Between current carrying terminals and exposed non-current carrying metal parts: 1.5 kV
Noise immunity±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunityMulfunction: 8 kV, Destruction: 15 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 980 m/s2, 3 times each in 6 directions Malfunction: 98 m/s2, 3 times each in 6 directions
Degree of protectionIP40 (panel surface)
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Ambient humidity rangeOperating: 35 to 85%
Life expectancy (relay output)Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1200 operations/h) Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Input signalsReset
No-voltage inputShort-circuit (ON) impedance: 1 kΩ max. Short-circuit (ON) residual voltage: 1 V max. Open circuit impedance: 500 kΩ min.
Operation start voltage30% max. of rated supply voltage
WeightApprox. 120 g