The Omron CP1L-L10DR-A PLC CPU Unit combines 6 digital inputs with 4 relay outputs for basic machine-control and compact industrial automation applications. This Programmable Logic Controller provides a 5K-step program capacity and supports 100 kHz high-speed counters across 4 axes for applications requiring fast input counting and sequence processing. The controller operates from an AC power supply and includes a built-in USB port for programming, configuration, and monitoring. Its relay output configuration provides electrical switching for connected control loads in small automated equipment. The CP1L-L10DR-A combines compact CPU control with high-speed counting and relay switching and belongs to the compact relay PLC range supporting Omron machine control systems.
20 MΩ min. (at 500 VDC) between the external AC terminals
and GR terminals
Dielectric strength
2,300 VAC at 50/60 Hz for 1 min between the external AC and
GR terminals, leakage current: 5 mA max.
Noise immunity
Conforms to IEC 61000-4-4. 2 kV (power supply line)
Vibration resistance
Conforms to JIS C60068-2-6. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for
80 minutes each. Sweep time: 8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistance
Conforms to JIS C60068-2-27. 147 m/s2 3 times each in X, Y, and Z directions
Ambient operating temperature
0 to 55°C
Ambient humidity
10% to 90% (with no condensation)
Ambient operating environment
No corrosive gas
Ambient storage temperature
−20 to 75°C (Excluding battery.)
Power holding time
10 ms min.
Function blocks
Maximum number of function block definitions: 128 Maximum number of instances: 256; Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length
1 to 7 steps per instruction
Instructions
Approx. 500 (function codes: 3 digits)
Instruction execution time
Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min
Common processing time
0.4ms
Inrush current *
100 to 120 VAC inputs:
20 A max. (for cold start at room temperature)
8 ms max.
200 to 240 VAC inputs:
40 A max. (for cold start at room temperature), 8 ms max.