+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

IP3312-B518 - Beckhoff Fieldbus Box And IO-Link Box

Technical Specifications of Beckhoff Fieldbus Box And IO-Link Box IP3312-B518:

Beckhoff IP3312-B518
BrandBeckhoff
Product TypeFieldbus Box And IO-Link Box
ProductIP3312-B518

IP3312-B518 Beckhoff Fieldbus Box And IO-Link Box Technical Specifications

SpecificationValue
Input filter5 variations, configurable
Power supply connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Bit width in the process imageinput: 4 x 16 bit data, optional: 4 x 8 bit control/status
Electrical isolationchannels/control voltage: 500 V, between the channels: no, control voltage/fieldbus: depends on the bus system
Digital peripheral signalsaccording to I/O type
Analog peripheral signalsaccording to I/O type
Configuration possibilitythrough KS2000 or the controller (service data objects)
Data transfer ratesautomatic detection of 10 kbaud up to 1Â Mbaud
Bus interface1 x M12 plug, 5-pin, 1 x M12 socket, 5-pin (tee-connector integrated)
Data transfer mediumshielded copper cable, 2 x signal, 1 x CAN ground (recommended)
Power supplycontrol voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type
Box supply current45 mA + current consumption of sensors, max. 0.5 A
Auxiliary power current 1according to I/O type
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL
Housing - Dimensions (W x H x D)30 mm x 210 mm x 26.5 mm
Housing - MaterialPA6 (polyamide)
Housing - Installation2 fixing holes 3.5 mm diameter for M3
Number of inputs4
Input connectionsM12, screw type
Resolution0.1°C per digit
Measurement error/uncertainty< ±0.5% (relative to full scale value)
Conversion timeapprox. 250Â ms, configurable up to 70 ms
Nominal voltage24 V DC (-15%/+20%)
Connection methodM12 socket, 2-wire connection for thermocouple
Sensor typestypes J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Measuring rangedepending on sensor type; preset value is type K, -100…+1370°C