+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact PSR-MC37-3NO-1NC-24DC-SC - 2702411 - Safety relays

Technical Specifications of Safety relays PSR-MC37-3NO-1NC-24DC-SC 2702411

BrandPhoenix Contact
Product TypeSafety Relays
ProductPSR-MC37-3NO-1NC-24DC-SC

Phoenix Contact Safety relays PSR-MC37-3NO-1NC-24DC-SC, 2702411 Technical Specifications

SpecificationValue
Note on applicationOnly for industrial use
Product typeSafety relays
Product familyPSRmini
ApplicationEmergency stop
Control1 and 2 channel
Mechanical service life10x 106 cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Overvoltage categoryII
Degree of pollution2
Typical response time< 100 ms (automatic start)
Typ. starting time with Us< 100 ms (when controlled via A1)
Typical release time< 20 ms (when controlled via A1 or S12 and S22.)
Restart time< 1 s (Boot time)
Recovery time< 500 ms
Maximum power dissipation for nominal condition17.03 W (UB = 30 V , US = 24 V , IS = 70 mA, IL2 = 72 A2, RContact = 0.2 )
Nominal operating mode100% operating factor
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between all current paths
Description of the inputnon-safety-related
Number of inputs1
Input voltage range "1" signal19.2 V DC ... 30 V DC
Inrush currentmin. 10 mA
Filter timemax. 3 ms (at S12, S22; test pulse width; blanking pulses/dark test)
Max. permissible overall conductor resistance150 Ω
Protective circuitSuppressor diode
Current consumption< 0.5 mA (typ. with US)
Output descriptionnon-safety-related
Number of outputs1 (digital)
Contact switching type1 signaling current path
Contact materialAgSnO2
Switching voltagemin. 5 V AC/DC
Switching capacitymin. 50 mW
Limiting continuous current1 A
Sq. Total current1 A2
Switching frequency0.5 Hz
Output fuse1 A gL/gG
pluggableyes
Connection methodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3
Status display3 x LED (green)
Operating voltage display1 x LED (green)
Width22.5 mm
Height112.2 mm
Depth114.5 mm
Color (Housing)yellow (RAL 1018)
Housing materialPA
Category4
Performance level (PL)e (5 A DC13; 5 A AC15; 8760 switching cycles/year)
Safety Integrity Level (SIL)3
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Ambient temperature (operation)-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g for Δt = 11 ms (continuous shock: 10g for Δt = 16 ms)
Vibration (operation)10 Hz ... 150 Hz, amplitude 0.15 mm, 2g
IdentificationCE-compliant
Mounting typeDIN rail mounting
Mounting positionvertical or horizontal
Rated control circuit supply voltage US24 V DC -20 % / +25 %
Rated control supply current IStyp. 70 mA
Power consumption at UStyp. 1.68 W
Input voltage range "0" signal< 5 V (S12)
Input current range "0" signal< 2 mA (S12)
Tightening torque0.5 Nm ... 0.6 Nm
Assembly noteSee derating curve
Maximum inrush current1 A (Δt = 5 ms at Us)
DesignationA1/A2
Voltage23 V DC (Us - 1 V)
Currentmax. 100 mA
Short-circuit protectionYes