+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact UT 2,5-TG-P/P BU - 3046582 - Disconnect terminal block

Technical Specifications of Disconnect terminal block UT 2,5-TG-P/P BU 3046582

BrandPhoenix Contact
Product TypeTerminal Block
ProductUT 2,5-TG-P/P BU

Phoenix Contact Disconnect terminal block UT 2,5-TG-P/P BU, 3046582 Technical Specifications

SpecificationValue
Product typeDisconnect terminal block
DIN rail/fixing supportNS 35/15
Number of connections2
Number of rows1
Potentials1
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Maximum power dissipation for nominal condition0.77 W
Number of connections per level2
Nominal cross section2.5 mm²
Stripping length9 mm
Internal cylindrical gageA3
Connection in acc. with standardIEC 6094771
Conductor cross section rigid0.14 mm² ... 4 mm²
Cross section AWG26 ... 12 (converted acc. to IEC)
Conductor cross section flexible0.14 mm² ... 4 mm²
Conductor cross section, flexible [AWG]26 ... 12 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.14 mm² ... 2.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.14 mm² ... 2.5 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 1.5 mm²
Maximum load current20 A (with 4 mm² conductor cross section)
Nominal voltage400 V (Current and voltage are determined by the plug used.)
Width5.2 mm
End cover width2.2 mm
Height57.8 mm
Depth on NS 35/7,547.5 mm
Depth on NS 35/1555 mm
Colorblue (RAL 5015)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 HL 3
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Test voltage setpoint1.89 kV
ResultTest passed
Requirement temperature-rise testIncrease in temperature ≤ 45 K
Short-time withstand current 2.5 mm²0.3 kA
Open side panelYes
DIN rail/fixing supportNS 35
Rotation speed10 (+/ 2) rpm
Revolutions135
Conductor cross section/weight0.14 mm² / 0.2 kg
Time of exposure30 s
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
Screw threadM3
Tightening torque0.5 ... 0.6 Nm
2 conductors with same cross section, solid0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible0.14 mm² ... 1.5 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.14 mm² ... 1.5 mm²
SpecificationDIN EN 50155 (VDE 0115200):201805
SpectrumLong life test category 2, bogiemounted
Frequencyf1 = 5 Hz to f2 = 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration5g
Test duration per axis5 h
Test directionsX, Y and Zaxis (pos. and neg.)
Pulse shapeHalfsine
Shock duration30 ms
Number of shocks per direction3
Rated cross section AWG12
Thermal continuous current Ith20 A (with 4 mm² conductor cross section)
GeneralCurrent and voltage are determined by the plug used.