+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Phoenix Contact UK 6-T-P - 3072800 - Test disconnect terminal block

Technical Specifications of Test disconnect terminal block UK 6-T-P 3072800

BrandPhoenix Contact
Product TypeTerminal Block
ProductUK 6-T-P

Phoenix Contact Test disconnect terminal block UK 6-T-P, 3072800 Technical Specifications

SpecificationValue
Product typeTest disconnect terminal block
DIN rail/fixing supportNS 32
Number of connections2
Number of rows1
Potentials1
Overvoltage categoryIII
Degree of pollution3
Rated surge voltage6 kV
Maximum power dissipation for nominal condition1.31 W
Number of connections per level2
Nominal cross section6 mm²
Stripping length10 mm
Internal cylindrical gageA5
Connection in acc. with standardIEC 6094771
Conductor cross section rigid0.5 mm² ... 10 mm²
Cross section AWG20 ... 8 (converted acc. to IEC)
Conductor cross section flexible0.5 mm² ... 6 mm²
Conductor cross section, flexible [AWG]20 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)0.5 mm² ... 6 mm²
Flexible conductor cross section (ferrule with plastic sleeve)0.5 mm² ... 6 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve0.5 mm² ... 4 mm²
Nominal current41 A
Maximum load current57 A (with 10 mm² conductor cross section)
Nominal voltage500 V
Width8.2 mm
End cover width2.2 mm
Height66.5 mm
Depth on NS 35/7,548 mm
Depth on NS 35/1555.5 mm
Colorgray (RAL 7042)
Flammability rating according to UL 94V0
Insulating material groupI
Insulating materialPA
Static insulating material application in cold60 °C
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 HL 3
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Open side panelYes
Ambient temperature (operation)60 °C ... 110 °C (Operating temperature range incl. selfheating; for max. shortterm operating temperature, see RTI Elec.)
Ambient temperature (storage/transport)25 °C ... 60 °C (for a short time, not exceeding 24 h, 60 °C to +70 °C)
Ambient temperature (assembly)5 °C ... 70 °C
Ambient temperature (actuation)5 °C ... 70 °C
Permissible humidity (operation)20 % ... 90 %
Permissible humidity (storage/transport)30 % ... 70 %
Mounting typeNS 35/7,5
Screw threadM3
Tightening torque1.5 ... 1.6 Nm
2 conductors with same cross section, solid0.5 mm² ... 2.5 mm²
2 conductors with same cross section, flexible0.5 mm² ... 4 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve0.5 mm² ... 2.5 mm²
Depth on NS 3253 mm
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Tightening torque disconnect slideM3 0.6 ... 0.8 Nm
Test socket torque0.6

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.