+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

ELX3202 - Beckhoff EtherCAT Terminal Analog Input

Technical Specifications of Beckhoff EtherCAT Terminal Analog Input ELX3202:

BrandBeckhoff
Product TypeEtherCAT Terminal Analog Input
ProductELX3202

ELX3202 Beckhoff EtherCAT Terminal Analog Input Technical Specifications

SpecificationValue
Number of inputs2 (differential)
Measurement error/uncertaintytyp. ≥ 10 kΩ (differential)
Input filter limit frequencytyp. 1 kHz
Measurement error/uncertainty 2< ±0.3% (relative to full scale value)
Housing - Design formcompact terminal housing with signal LEDs
Housing - Materialpolycarbonate, blue
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.08....2.5mm²,st*: 0.08...2.5mm²,f*: 0.14....1.5 mm²
Housing - Connection cross-section AWGs*: AWG28...14,st*: AWG28...14,f*: AWG26...16
Housing - Stripping length8…9 mm
Power supplyvia the E-bus
Conversion time10…3300 ms (adjustable, default: 170 ms)
Current consumption E-bustyp. 70 mA
Special featureslimit value monitoring, digital filter and characteristic curve linearization integrated, connection method freely configurable
Weightapprox. 60 g
Operating temperature-25....+60°C
Storage temperature-40....+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/see documentation
Approvals/markingsCE, UL, ATEX, IECEx, cFMus, CCC
Current consumption power contactstyp. 10 mA
Ex markingATEX:  II 3(1)G Ex ec [ia Ga] IIC T4 Gc  II (1)D [Ex ia Da] IIIC  I (M1) [Ex ia Ma] IIECEx:  Ex ec [ia Ga] IIC T4 Gc  [Ex ia Da] IIIC  [Ex ia Ma] IcFMus:  AIS Class I, II, III, Division 1, Groups A thru G  Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc  [AEx ia Da] IIIC T4
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (10 Ω…4 kΩ), KT(Y) sensors
Connection method2-, 3-, 4-wire (default: 2-wire)
Measuring current< 1 mA (depending on sensor and measuring range)
Temperature range-200…+850°C (Pt sensors); -60…+250°C (Ni sensors), for further types and details see documentation

Disclaimer: IndMALL serves solely as a platform connecting buyers and vendors. It does not participate in pricing, payment, or delivery of goods.
Buyers are advised to verify all details and deal directly with vendors before finalizing any transaction.