+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

EL3632 - Beckhoff EtherCAT Terminal Analog Input

Technical Specifications of Beckhoff EtherCAT Terminal Analog Input EL3632:

Beckhoff EL3632
BrandBeckhoff
Product TypeEtherCAT Terminal Analog Input
ProductEL3632

EL3632 Beckhoff EtherCAT Terminal Analog Input Technical Specifications

SpecificationValue
Number of inputs2
Input filter limit frequencyanalog parameterizable 5thorder low-pass filter up to 25 kHz, typically 0.05 Hz high-pass filter
Measurement error/uncertainty 2< ±0.5% (DC; relative to full scale value)
Housing - Design formcompact terminal housing with signal LEDs
Housing - Materialpolycarbonate
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.08..2.5 mm²,st*: 0.08...2.5 mm²,f*: 0.14..1.5 mm²
Housing - Connection cross-section AWGs*: AWG28..14,st*: AWG28..14,f*: AWG26...16
Housing - Stripping length8…9 mm
Housing - Current load power contactsImax: 10 A
Distributed clocksyes
Conversion time20 μs (max. 50 ksamples/s)
Current consumption E-bustyp. 220 mA
Special featuresautomatic anti-aliasing function, wire breakage detection
Weightapprox. 60 g
Operating temperature-25...+60°C
Storage temperature-40....+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/see documentation
Approvals/markingsCE, CCC, UL, ATEX, IECEx
Current consumption power contacts24 V, typ. 20 mA + load
Ex markingATEX:II 3 G Ex ec IIC T4 GcIECEx:Ex ec IIC T4 Gc
Measuring rangedefault ±5 V up to 25 kHz, ±250 mV up to 10 Hz