EL3255 - Beckhoff EtherCAT Terminal Analog Input

Technical Specifications of Beckhoff EtherCAT Terminal Analog Input EL3255:

Beckhoff EL3255
BrandBeckhoff
Product TypeEtherCAT Terminal Analog Input
ProductEL3255

EL3255 Beckhoff EtherCAT Terminal Analog Input Technical Specifications

SpecificationValue
Number of inputs5
Ground reference (input)single-ended
Measurement error/uncertainty>> 100 kΩ to wiper connection
Input filter limit frequencytyp. -3 dB at 3 kHz and potentiometer 50 kΩ
Measurement error/uncertainty 2< ±0.5% (relative to full scale value)
Housing - Design formHD (High Density) housing with signal LEDs
Housing - Materialpolycarbonate
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.08..2.5 mm²,st*: 0.08...2.5 mm²,f*: 0.14..1.5 mm²
Housing - Connection cross-section AWGs*: AWG28..14,st*: AWG28..14,f*: AWG26...16
Housing - Stripping length8…9 mm
Housing - Current load power contactsImax: 10 A
Power supplyvia power contacts
Conversion timetyp. 300…700 µs, dependent on settings, default setting: approx. 500 µs (5 channels, filter deactivated)
Electrical isolation500 V (E-bus/field potential)
Current consumption E-bustyp. 80 mA
Bit width in the process image5 x 16 bit input
Configurationno address setting, configuration via the controller
Special featuresopen-circuit recognition, supply monitoring, activatable filters, simultaneous measurement of the channels
Weightapprox. 70 g
Operating temperature-25…+60°C
Storage temperature-40…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, CCC, UL, ATEX, IECEx
Current consumption power contactsdependent on the potentiometers, max. 70 mA
Ex markingATEX:II 3 G Ex ec IIC T4 GcIECEx:Ex ec IIC T4 Gc
Sensor typespotentiometer 300 Ω…50 kΩ
Measuring rangepotentiometer 300 Ω…50 kΩ
Feed voltage potentiometertyp. 10 V ±10%
Output currentmax. 0.3 A total supply current for the potentiometers
Wiring fail indicationyes