+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

EL2212 - Beckhoff EtherCAT Terminal

EL2212 Beckhoff EtherCAT Terminal Technical Specifications

Beckhoff EL2212
BrandBeckhoff
Product TypeEtherCAT Terminal
ProductEL2212

EL2212 Beckhoff EtherCAT Terminal Technical Specifications

SpecificationValue
Connection technology4-wire
Nominal voltage24…72 V DC (-15%/+0%)
Distributed clocksyes
Current consumption power contactsload-dependent
Current consumption E-bustyp. 120 mA
Electrical isolation500 V (E-bus/field potential)
Configurationvia TwinCAT System Manager
Special featuresMulti-timestamping, current-controlled outputs can be connected in high-resistance mode.
Weightapprox. 50 g
Operating temperature0…55°C
Storage temperature-25…+85°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE
Housing - Design formcompact terminal housing with signal LEDs
Housing - Materialpolycarbonate
Housing - Dimensions (W x H x D)12Â mm x 100Â mm x 68 mm
Housing - Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Housing - Side by side mounting by means ofdouble slot and key connection
Housing - Markinglabeling of the BZxxxx series
Housing - Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Housing - Connection cross-sections*: 0.08…2.5 mm²,st*: 0.08…2.5 mm²,f*: 0.14…1.5 mm²
Housing - Connection cross-section AWGs*: AWG28...16,st*: AWG22...16,f*: AWG26...19
Housing - Stripping length8…9 mm
Housing - Current load power contactsImax: 10 A
Short-circuit currenttyp. 12 A
Precision of timestamp in the terminal10 ns
Distributed clock precision<< 1 µs
Resolution timestamp1 ns
Load typeinductive > 1 mH
Max. output currentpeak current: max. 10 A per channel,holding current: 0.2…2.5 A per channel
Output stagefull bridge (push-pull)
Reverse voltage protection–
Switching timeswithout distributed clocks: typ. TON/TOFF20 µs,with distributed clocks: typ. TON/TOFF< 1 µs via internal compensation