+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Delta DRF-24V480W3GTA: 20A 480W DIN Rail Power Supply

Technical Specifications of Delta 20A 480W DIN Rail Power Supply DRF-24V480W3GTA:

Delta DRF-24V480W3GTA
Output Current20A
Output Voltage24V
Output Power480W
Input Current< 0.85 A @ 3 x 400 Vac, < 0.73 A @ 3 x 500 Vac

Delta 20A 480W DIN Rail Power Supply DRF-24V480W3GTA Technical Specifications:

SpecificationValue
Output Current20A
Output Voltage24V
Output Voltage Adjustment Range24-28 Vdc
Output Power480W
Line Regulation< 40 mV (@ 3 x 320-575 Vac input, 100% load)
Load Regulation< 200 mV (@ 3 x 320-575 Vac input, 0-100% load)
PARD< 150 mVpp
Start-up Time1,000 ms typ. @ nominal input (100% load)
Hold-up Time20 ms typ. @ 3 x 400 Vac & 500 Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)± 5% @ 3 x 320-575 Vac input, 1.5-100% load (Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 1 kHz)
Start-up with Capacitive Loads20,000 µF Max
Rise Time100 ms typ. @ nominal input (100% load)
Nominal Input Voltage3 x 380-500 Vac
Input Voltage Range3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
Nominal Input Frequency50-60 Hz
Input Frequency Range47-63Hz
DC Input Voltage Range450-800 Vdc
Input Current< 0.85 A @ 3 x 400 Vac, < 0.73 A @ 3 x 500 Vac
Input Power (Standby Mode)-
Efficiency at 100% load94.0% typ. @ 3 x 400 Vac & 500 Vac
Inrush Current35 A typ. @ 3 x 400 Vac & 3 x 500 Vac
Power Factor at 100% load> 0.90 @ 3 x 400 Vac, > 0.88 @ 3 x 500 Vac
Leakage Current< 3.5 mA @ 3 x 500 Vac
Case Chassis / CoverAluminun
IndicatorGreen LED DC OK
Cooling SystemConvection
Input Terminal4 Pins (Rated 600 V / 30 A)
Output Terminal4 Pins (Rated 600 V / 30 A)
Signal Terminal2 Pins (Rated 300 V / 12 A)
Noise Sound Pressure Level (SPL)< 25dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715
WireInput: AWG 18-10 Output: AWG 12-10 DC OK: AWG 20-16
Unit Weight1.20 kg (2.65 lb)
Vibration (Operating)IEC 60068-2-6, Sine Wave: 10-500 Hz; 3G peak; 60 min per axis for all X, Y, Z directions
Operating Temperature3-Phase -25°C to +70°C (-40°C Cold Start) 2-Phase -25°C to +60°C (-40°C Cold Start)
Storage Temperature-40°C to +85°C
Power De-ratingVertical Mounting: > 55°C de-rate power by 3.33% / °C Horizontal Mounting: > 25°C de-rate power by 2.5% / °C Input Voltage: 2-Phase 2 x 340-575 Vac de-rate power to 80%
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction
Operating AltitudeOVC III 0 to 2,500 Meters (8,200 ft.) OVC II 2,500 to 6,000 Meters (19,680 ft.) 0 to 5,000 Meters (16,400 ft.)
Pollution Degree2
Over Voltage CategoryIEC/EN 62477-1, EN 60204-1, IEC 62103 OVC III: 0 to 2,500 Meters (8,200 ft.) OVC II: 2,500 to 6,000 Meters (19,680 ft.) IEC/EN 62368-1, IEC/EN 61010 OVC II: 0 to 5,000 Meters (16,400 ft.)
Get A Quote for Delta 20A 480W DIN Rail Power Supply DRF-24V480W3GTA at the best price. Here are the brief Technical Specifications of DRF-24V480W3GTA are 20A Output Current, 24V Output Voltage, 480W Output Power at competitive prices. It operates with a nominal input voltage of 3 x 380-500 Vac and supports an input voltage range of 3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase). The power supply covers a nominal input frequency of 50-60 Hz, with a broader input frequency range of 47-63Hz. For DC input, it accepts a range from 450-800 Vdc. With an input current of < 0.85 A @ 3 x 400 Vac, < 0.73 A @ 3 x 500 Vac, it ensures efficient performance. The unit features a Green LED DC OK indicator, aiding in quick status checks. Both input and output terminals have 4 Pins (Rated 600 V / 30 A) for secure connections. Designed for extreme environments, it operates from 3-Phase -25°C to +70°C (-40°C Cold Start) 2-Phase -25°C to +60°C (-40°C Cold Start) and has a storage temperature range of -40°C to +85°C. It's Time to get a Quote for your requirement of 20A 480W DIN Rail Power Supply. We guarantee unmatched pricing and unparalleled support compared to other Distributors.