LP4K12004BW3: Schneider TeSys K 4P Contactor 24VDC Coil

Technical Specifications of Schneider TeSys K 4P Contactor 24VDC Coil LP4K12004BW3:

Schneider Electric LP4K12004BW3
Power pole contact composition4 NO
Control Circuit TypeDC wide range
Inrush power in W1.8 W 68 °F (20 °C))
Connection Terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable endPower circuit screw clamp terminals 2 0.002 in² (1.5 mm²)flexible with cable end

Schneider TeSys K 4P Contactor 24VDC Coil LP4K12004BW3 Technical Specifications:

SpecificationValue
RangeTeSys
Product or Component TypeContactor
Device short nameLP4K
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
Power pole contact composition4 NO
[Ue] rated operational voltagePower circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type [Uc]DC wide range
Control circuit voltage24 V DC
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 140 °F (60 °C)) for power circuit10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity144 A AC for power circuit conforming to IEC 60947
Rated breaking capacity110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current115 A 122 °F (50 °C) - 1 s for power circuit105 A 122 °F (50 °C) - 5 s for power circuit100 A 122 °F (50 °C) - 10 s for power circuit75 A 122 °F (50 °C) - 30 s for power circuit55 A 122 °F (50 °C) - 1 min for power circuit50 A 122 °F (50 °C) - 3 min for power circuit25 A 122 °F (50 °C) - >= 15 min for power circuit
Associated fuse rating25 A gG at <= 440 V for power circuit25 A aM for power circuit
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Power circuit 600 V CSA C22.2 No 14
Inrush power in W1.8 W 68 °F (20 °C))
Hold-in power consumption in W1.8 W 68 °F (20 °C)
Heat dissipation1.8 W
Control circuit voltage limitsOperational: 0.7...1.3 Uc (at <122 °F (50 °C))Drop-out: >= 0.10 Uc (at <122 °F (50 °C))
Connections - terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable endPower circuit screw clamp terminals 2 0.002 in² (1.5 mm²)flexible with cable end
Maximum operating rate3600 cyc/h
Mounting SupportPlateRail
Operating time30...40 ms coil energisation and NO closing10 ms coil de-energisation and NO opening
Height2.3 in (58 mm)
Width1.8 in (45 mm)
Depth2.2 in (57 mm)
Net Weight0.518 lb(US) (0.235 kg)
IP degree of protectionIP2X
Ambient air temperature for operation-13…122 °F (-25…50 °C)
Ambient Air Temperature for Storage-58…176 °F (-50…80 °C)
Operating altitude6561.68 ft (2000 m) without derating
Please speak to our Technical Engineer for Schneider TeSys K 4P Contactor 24VDC Coil LP4K12004BW3 at attractive prices. Technical Specs Summary of LP4K12004BW3 includes Contactor Product or Component Type 4 NO power pole contact composition. This contactor operates with a rated operational voltage of up to Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz, ensuring flexibility in various industrial applications. The control circuit operates on a DC wide range with a control voltage of 24 V DC, providing reliable control functionality. It has a rated impulse withstand voltage of 8 kV, conforming to industry standards for electrical safety. The compact design includes a height of 2.3 in (58 mm), a width of 1.8 in (45 mm), and a depth of 2.2 in (57 mm). Match Your Needs with a Quote for your requirement of Schneider TeSys K 4P Contactor 24VDC Coil. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.