+91 79955 44066
IndMALL: B2B Marketplace - We Connect Buyers & Sellers for Industrial Products

Pepperl Fuchs KFU8-CRG2-Ex1.D Trip Amplifier

The Pepperl Fuchs KFU8-CRG2-Ex1.D Trip Amplifier offers a Analog input signal type, signal, relay output, and screw terminals connection. Manufactured by Pepperl Fuchs under the P&F Trip Amplifier category.

BrandPepperl Fuchs
Product TypeTrip Amplifier
Model NumberKFU8-CRG2-Ex1.D

Pepperl Fuchs KFU8-CRG2-Ex1.D Trip Amplifier – Technical Specifications

SpecificationValue
Signal typeAnalog input
Safety Integrity Level (SIL)SIL 2
Supply Connectionterminals 23, 24
Rated voltage20 ... 90 V DC or 48 ... 253 V AC
Ripple-
Rated current-
Power dissipation2 W / 3 VA
Power consumption2.2 W / 4 VA
Programming Interfaceprogramming socket
Connection side (Input)field side
Connection (Input)terminals 1, 2, 3
Input signal0/4 ... 20 mA
Available voltage> 15 V at 20 mA
Open circuit voltage/short-circuit current (Input)24 V / 33 mA
Input resistance45 Ω (terminals 2, 3)
Line fault detectionbreakage I < 0.2 mA; short-circuit I > 22 mA
Connection side (Output)control side
Connection (Output)output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-
Output signal0 ... 20 mA or 4 ... 20 mA
Output I, IIsignal, relay
Output IIISignal, analog
Input/Other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective errorreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply and collective errorreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons via PACTware
Labelingspace for labeling at the front
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/35/EUEN 61010-1:2010
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificateTÜV 01 ATEX 1701
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC Ex-Hexagon II (1)D [Ex ia Da] IIIC Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Maximum safe supply voltage253 V AC (Attention! The rated voltage can be lower.)
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
IECEx certificateIECEx TUN 09.0007
UL approval-
FM approval(Control drawing)16-554FM-12 (cFMus)
Ask for the Pricing of P&F Line Fault Detection Trip Amplifier KFU8-CRG2-Ex1.D at unbeatable prices. Detailed Specifications of Ex ia features Analog input with 0/4 ... 20 mA range, SIL 2 and terminals 23, 24 ratings. Operating on 20 ... 90 V DC or 48 ... 253 V AC via terminals 23, 24 and it consumes 2.2 W / 4 VA. The amplifier features programming sockets, reinforced insulation, and functional insulation rated at 50 Veff. Outputs include multiple terminals for signal, relay. The unit operates between -20 ... 60 °C (-4 ... 140 °F), has an IP50 rating, and mounts on a 55 mm DIN rail. Measuring 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 , and weighing 300 g, it includes LEDs, a display, and control panel for easy operation. Now's the Time to Secure a Quote for your requirement of P&F Line Fault Detection Trip Amplifier. We're committed to offering more favorable pricing and more responsive support than other Traders.